DEFINITION

RVU Ser es 12-24kV Vacuum C rcu t Breaker s a three-phase AC ndoor breaker w th 12-24kV rated voltage su table for
a r nsulated sw tchgear and can be appl ed n controll ng and protect ng electr cal equ pment n ndustr al and m neral
enterpr ses, power plants and substat ons. Operat on mechan sm s nstalled laterally.
The product conforms to the IEC 62271-100 standard. Short c rcu t type tests are performed n KEMA H gh Power Laboratory
n the Netherlands. RVU ser es prov de safe and rel able performance. The embedded poles of RVU have the techn que of
vent lat on and convect on. Bes des the vacuum nterrupter has low res stance and h gh number of short c rcu t break ng.
AII of that reduce the power consumpt on and the temperature r s ng due to the longt me runn ng of c rcu t breaker.
RVU 12-24kV VACUUM CIRCUIT BREAKER
Under normal cond t ons the nterrupter s n closed pos t on.
Arc ng s occured w th n the nterrupter by w thdraw ng the
mov ng contact from stat onary contact. Th s arc burns n the
metal vapor evaporated from local hot spots on the contact
surfaces. The metal vapour cont nually leaves the nter-contact
reg on and recondenses on the contact surfaces and surround ng
metal vapor condensat on sh eld. The latter s usually solated
from both contacts and serves to protect the glass or ceram c
envelope from vapor depos t on. At current zero, vapor product on
ceases and the or g nal vacuum cond t on s rap dly approached.
The d electr c strength of the nterrupter also ncreases, and the
c rcu t s nterrupted.