Electrical
installation
4.4
Connections
The order of the connections to the connector no. or the connection terminals is obligatory.
The input and output conductors may be altered or supplemented in accordance with the
electrical standards. All further advice is non-obligatory.
Adhere to:
- Connections and operating instructions
- Local regulations
- EU guideline 89/392/EWG
- VDE and TÜV regulations and Trade body guidelines
The controllers are delivered with an auxiliary
voltage input for 230 or 400V~.
The current consumption is 0.1 A.
The fuses F1 and F2 are rated for field current
(2.5 A f).
Auxiliary voltage and field supply are both
connected to the plug-in terminal X5.
The phase position of the auxiliary voltage and the
power supply voltage must correspond to each
other.
X5:14 corresponds to terminal 15 and X5:17
corresponds to terminal 16.
Field voltage
230 V~ connection equal to 210 V
400 V~ connection equal to 360 V
=
210 V
to N across terminal X5:18
The max. field current is 1.5 A.
The field current is not monitored.
In case the field fuse F1 fails the
device is switched off.
Note:
Observe the type plate / control voltage XXX
Classic Q1
4-4 Q1-Q2-Hilfsspannung-1
=
=
or
4-5 Q1-Q2Feld230-210-1
4-6 Q1-Q2-Feld-400-210-1
4-7 Q1-Q2-Feld400-360-1
13