Connecting The Power Supply - Pro-face ST3000 Series Hardware Manual

Hide thumbs Also See for ST3000 Series:
Table of Contents

Advertisement

ST3000 Series Hardware Manual
4.2.2

Connecting the Power Supply

This section describes the precautions for supplying a power voltage.
Twisted-pair cord
Constant
Voltage
Transformer
Twisted-pair cord
Insulating
Transformer
Main Power
ST Power
Input/Output
Power
ST
Main
Power
Power
T1
T2
Input/
Output
Power
Main Circuit
E1
4-10
ST
FG
ST
FG
ST
Input/Output
Unit
ST
Input/Output
Unit
Input/Output
Unit
Operation
Unit
ST
FG
E2
Lightening Surge
Absorber
• If the supplied voltage exceeds the ST unit's range,
connect a constant voltage transformer.
SEE
Chapter 3 Specifications (page 3-1)
• For between the line and ground, select a power supply
that is low in noise. If there is an excess amount of noise,
connect a insulating transformer.
• Use constant voltage and
insulating transformers with
capacities exceeding Power
Consumption value.
• When supplying power to the ST unit, be sure to
separate the input/output and power lines, as shown.
• To increase the noise resistance quality of the power
cord, simply twist each power wire before attaching the
Ring Terminal.
• The power supply cable must not be bundled or
positioned close to main circuit lines (high voltage, high
current), or input/output signal lines.
• Connect a lightening surge absorber, as shown in the
diagram, to deal with power surges.
• To avoid excess noise, make the power cord as short as
possible.
• 24V DC input unit is must be used with a Class 2 power
supply.
• Be sure to ground the surge
absorber (E1) separately from
the ST unit (E2).
• Select a surge absorber that
has a maximum circuit
voltage greater than that of
the peak voltage of the power
supply.