Figure 3-2 Water trap installation
Electrical access check for auxiliary engineering equipment
The modular indirect evaporative cooling system is important equipment for air
processing. You need to strictly follow the HVAC construction requirements. To
ensure NetCol8000 proper operation, protect it against dust, dirt, corrosive gas,
and high humidity. Do not use the indoor unit in open air.
Engineering connection precautions

3.2 Material Preparations

Materials are classified to Huawei-provided, self-purchased, and onsite prepared
materials, which are marked as mandatory, optional, and engineering purchasing
in this document.
Issue 06 (2020-08-19)
NO TE
● When the device is under negative pressure: H1 = H2 ≥ P/10 + 20 mm.
● P: absolute static pressure at the water pan drain port, measured in Pa.
NO TICE
Air channel installation: Install a flexible pipe between the NetCol8000 and
the air channel connector. The weight of the NetCol8000 is not borne by the
air channel. Engineering air channels need to be supported to ensure that the
air channels and NetCol8000 connections are not forced.
Pipe thermal insulation: Take thermal insulation measures for all inlet and
outlet pipes of the NetCol8000. Leave space for operating and maintaining
thermal insulation for valves and joints. Take insulation measures at low
temperatures to prevent freezing in the water pipe.
Mandatory: mandatory configuration. This material is provided by Huawei
and can be found in delivered fittings.