Huawei NetCol8000-E220 User Manual page 92

Modular indirect evaporative cooling system
Hide thumbs Also See for NetCol8000-E220:
Table of Contents

Advertisement

NetCol8000-E220 Modular Indirect Evaporative
Cooling System
User Manual
Menu
Settings > Quick
Settings > T/H
Settings
Issue 06 (2020-08-19)
Parameter
Temperature
and humidity
control type
Temperature
setpoint
Humidity
setpoint
Cold aisle
sensor 1–5
Hot aisle
sensor 1–5
Copyright © Huawei Technologies Co., Ltd.
4 Power-on and Commissioning
Setting Guide
alarms are open and
generate no alarms.
● When the application
scenario is cold or hot
aisle containment,
you are advised to
choose Cold aisle if
the cold aisle T/H
sensors are
configured, and
choose Supply air if
the cold aisle T/H
sensors are not
configured.
● When the application
scenario is non-aisle
containment, you are
advised to choose
Return air, and
choose Cold aisle if
the cold aisle T/H
sensors are
configured.
● Hot aisle is not
recommended.
After the Temperature
and humidity control
type and the
temperature value under
this type are set, the
device runs based on the
settings.
After the Temperature
and humidity control
type and the humidity
value under this type are
set, the device runs
based on the settings.
If a temperature and
humidity sensor outside
the cabinet is installed,
set the temperature and
humidity sensor in the
corresponding position to
Enable.
Default Value
Return air
25ºC
50% RH
Disable
Disable
83