Installation and Commissioning Instructions Power supply according to EN12101-10 and Control Unit according to prEN12101-9 SHEV - C EMB 8000+ (5A / 10A / 24A / 48A / 72A) ontrol tested electrical control device EMB 8000+ with recognition number G512005...
Page 2
ontents Abbreviations Warning and Safety Symbols Target Groups, Intended Use Safety Instructions, Guidelines and Standards 3 - 6 Overview: EMB 8000+ in the installation Overview: EMB 8000+ module 7 - 8 Technical Data Preparing assembly Information regarding equipment and version of Control Unit Arrangement, order and connection of modules on standard rail 9 - 13 Connection: Main power supply...
Page 3
refaCe emark bbreviAtions Index of abbreviations Scale units These abbreviations are used consistently throughout this instruction. °C Degree Celsius Unless stated differently, all dimensions indicated in this document are in mm. Amperes General tolerances in accordance with DIN ISO 2768-m. Amp-hours Surface mounting Kilogram...
Page 4
refaCe emark Arget group These instructions are intended for personnel trained in This device is not intended for use by per- electrical engineering and skilled operators of systems sons (including children) with physical, Arning for natural smoke ventilation (NRA / SHEV) (natural smo- sensory or mental limitations or lacking ke exhaust system / smoke and heat exhaust system) and experience and / or knowledge.
Page 5
afety nstruCtIons Afety instructions It is important to follow these instruc- Cables must be laid such way that they cannot tions for the safety of persons. These be sheared off, twisted or bent during operati- Arning instructions must be kept in a safe place on.
Page 6
afety nstruCtIons Modifiable standard configurations are parti- Declaration of Conformity cularly emphasized in these instructions. The The control device is manufactured and inspected for functional range of the unlicensed version can its intended use in accordance with the European guide- be expanded by activation against payment lines.
Page 7
reParIng ssembly : emb 8000+ vervieW NHXH-FE 180 / E 90 min. 3 x 1,5mm Note: Number depends on the configuration of the modules. JE-H (St) H FE 180 / E 90 external 2 x 2 x 0,8 fire alarm system JE-H (St) H FE 180 / E 90 J-Y (St) Y - 2 x 2 x 0,8 (Button without display) 2 x 2 x 0,8...
Page 8
reParIng ssembly : emb 8000+ m vervieW odule JE-H (St) H FE 180 / E 90 JE-H (St) H FE 180 / E 90 2 x 2 x 0,8 mm, max. 400 m 2 x 2 x 0,8 mm, max. 400 m max.
Page 9
reParIng ssembly echnicAl Electrical data and connected loads Environmental Conditions (operation) Operating voltage, primary: 195…..253 V AC Ambient temperature range: -5…+40 °C Frequency: 50….60 Hz Maximum relative air (according to EN 12101 Class 1) Current consumption (primary): (depending on version) humidity: 75 % (mean value over lifetime) Output voltage of switching...
Page 10
reParIng ssembly xpansion imitation ystEm imits The following key data must be taken into account when Due to the hardware and software, the EMB 8000+ is dimensioning SHEV Control Units: limited by the following points. Configuration using the software is guaranteed within these limits. •...
Page 11
reParIng ssembly otes on the ontrol nit equipment And version Determining the right equipment for the Calculating: maximum allowable number of Control Unit modules In order to be able to determine the right version and equipment of In order to guarantee a high degree of adaptability to the variety of structural requirements, the emB 8000+ is designed as a modular the Control Unit without a problem, the following procedure is recom- mended:...
Page 12
reParIng ssembly Main functions of the modules: Following module requirement as an example • The Power-Module PM provides - depending on the switching power supply - 5 a, 10 a or 24 a. • One Power-Module-Extension PME provides an additional 24 a. 34,0 •...
Page 13
reParIng ssembly rrAngement order And connection of modules on the stAndArd rAil Arrangement and order of modules Connection of modules The modules are mounted on the standard rail directly next to each other. When connecting the modules, one must differentiate between three kinds of connections: Following module arrangement must be absolutely adhered to: Connection to the main power supply of...
Page 14
nstallatIon step onneCtIon ower uPPly nstallatIon step onnection Ain poWer supply The max. power consumption per Drive-Modules DM / DMX / IDM, which can be connected to a switching Only connect when disconnected from the mains pow- power supply with PM or PME depends on the respective er supply! Switch off power supply and secure against switching power supply (5 a, 10 a, 24 a).
Page 15
nstallatIon step onneCtIon ower uPPly Connection of main power supply: 10 a 24 a Power-Module pm with one switching power supply 10 a or 24 a Fuse Fuse with 10 a Operation display (green) Operation display (green) 10 a or 24 a Status display (green) Fault display (yellow) Fault display (yellow)
Page 16
nstallatIon step onneCtIon odules 10 a 24 a 48 a 72 a nstallatIon step onnection odules to Since we are dealing with a digital BUS, the modules can be intercon- nected with the ribbon cable on the bottom of the module independent Only connect when disconnected from the mains of their function within the system.
Page 17
nstallatIon step etworkIng ontrol 3: n nstallatIon step Etworking of ontroL Basics: Up to 30 EMB 8000+ Control Units can be networked with one another stub lines or ring lines are not permitted. The shield of the bus cable via the „OnBoard“ CAN bus interface. The maximum cable length for the may only be connected on one side (asymmetrical), the ground of two entire bus segment is 400 meters (cable type Y-ST-Y 2 x 2 x 0.8 mm).
Page 18
nstallatIon step etworkIng ontrol Connection diagram: CAN-composite Connection diagram: CAN-composite First Control Unit Control Unit(s) Last Control Unit Switch position: Switch position: Switch position: Slider towards LAN connector Slider towards Slider towards LAN connector CAN-BUS terminal terminal Cable type to be used: Y-ST-Y 2x2x0,8mm, Twisted pair cable with shield...
Page 19
nstallatIon step etworkIng ontrol CAN Checklist CAN Checklist What you should definitely check before you configure. If a repeater is used (due to the length of the cable), the following must also be checked: ❐ Are all Control Units switched on / under voltage? ❐...
Page 20
vervIew onneCtIon xternal omPonents 10 a 24 a 48 a 72 a vervieW of connection of externAl components Line length and cross-section A (drives) depend on the type of drive and Allowable connection values: on the number of drives. Line length and cross-section can be determined from the following formula: a = display, max.
Page 21
vervIew onneCtIon xternal omPonents 10 a 24 a 48 a 72 a Connection: Power-Module PM Connection: IM-K max. 0,5 A 24 V DC Indicators´ side In 6 In 5 In 4 In 3 24 V DC In 2 System voltage In 1 (back-up battery cached) (back-up battery not cached)
Page 22
vervIew onneCtIon xternal omPonents 10 a 24 a 48 a 72 a Connection: Drive-Module DM / DMX Connection: Intelligent-Drive-Module IDM DMX = without terminal Drives S12 24 V DC Line end IDM = 10 A module Drives 24 V DC DM = max.
Page 23
nstallatIon step onneCtIon ower odule xtensIon nstallatIon step oWer odule xtension Power-Module-Extension PME Part.-No.: 688100 Application: Module for the self installation on customer side into the SHEV Control Unit EMB 8000+ for monitoring of the main power supply. Operating voltage: 24 V DC Internal consumption: 0 mA...
Page 24
onneCtIon ower odule xtensIon 10 a 24 a 48 a 72 a Connection: Power-Module-Extension PME from PME 2 PM / PME 1 Operation display (green) Status display (green) next DM(X) Back-up batteries Power supply Installation instruction SHEV - Control Unit EMB 8000+...
Page 25
nstallatIon step onneCtIon ower odule nstallatIon step oWer odule xtension Power-Module PM Part.-No.: 688050 Application: Module for the self installation on customer side into the SHEV Control Unit EMB 8000+ for monitoring of the main power supply. Operating voltage: 24 V DC Internal consumption: 16,1 mA Housing (WxHxD):...
Page 26
onneCtIon ower odule 10 a 24 a 48 a 72 a Connection: Power-Module PM System voltage (cached by back-up batteries) max. 0,5 A Voltage (not cached by back-up batteries) Connection to PME 1 The use of back-up battery cached system voltage may demand larger Operation display (green) batteries Status display (green)
Page 27
nstallatIon step onneCtIon ontrol odule 5: c nstallatIon step ontrol odule Control-Module CM Part.-No.: 688120 Application: Module for the self installation on customer side into the SHEV Control Unit EMB 8000+ for the connecting of automatic smoke detectors and break-glass units. Operating voltage: 24 V DC Detector line voltage:...
Page 28
onneCtIon ontrol odule 10 a 24 a 48 a 72 a Connection: Control-Module CM Signalling line 1 Signalling line 2 Signalling line 3 Automatic smoke detector or Break-glass unit (manual fire alarm) triggering of external fire alarm unit Resistance R must remain in the last or only detector.
Page 29
nstallatIon step onneCtIon ensor odule 6: s nstallatIon step ensor odule Sensor-Module SM Part.-No.: 688150-9 Part.-No.: 688150 Application: Factory fitted module installed into an Application: Module for the self installation on SHEV Control Unit EMB 8000+ and fully wired, for the customer side into the SHEV Control Unit EMB 8000+ connecting of automatic smoke detectors and for the connecting of automatic smoke detectors and...
Page 30
onneCtIon ensor odule 10 a 24 a 48 a 72 a Connection: Sensor-Module SM Signalling line 1 Signalling line 2 Signalling line 3 (manual fire alarm) Break-glass unit Automatic smoke detector or triggering of external fire alarm unit Resistance R E must remain in the last or only detector.
Page 31
nstallatIon step onneCtIon rIve odule nstallatIon step rive odule 10 a Drive-Module DM Part.-No.: 688250-9 Part.-No.: 688250 Application: Factory fitted module installed into an Application: Module for the self installation on SHEV Control Unit EMB 8000+ and fully wired, for the customer side into the SHEV Control Unit EMB 8000+ controlling of drives, gas-pressure generators and mag- for the controlling of drives, gas-pressure generators and...
Page 32
onneCtIon rIve odule 10 a Connection: Drive-Module DM (10a) Automatic Ventilation Drives 24 V DC Ventilation control push button OPEN CLOSE max. max. Stop 400 m 10 pieces configurable Drive line with fixed-temperature heat detector e.g. re-registration CLOSE CLOSE potential-free contact Drive line OPEN OPEN...
Page 33
nstallatIon step onneCtIon rIve odule nstallatIon step rive odule 20 a Drive-Module DMX Part.-No.: 688255-9 Part.-No.: 688255 Application: Factory fitted module installed into an Application: Module for the self installation on SHEV Control Unit EMB 8000+ and fully wired, for the customer side into the SHEV Control Unit EMB 8000+ controlling of drives, gas-pressure generators and mag- for the controlling of drives, gas-pressure generators and...
Page 34
onneCtIon rIve odule 20 a Connection: Drive-Module DMX (20a) Automatic Ventilation Drives 24 V DC Ventilation control push button OPEN CLOSE max. max. Stop 400 m 10 pieces configurable Drive line with fixed-temperature heat detector e.g. re-registration CLOSE CLOSE potential-free contact Drive line OPEN OPEN...
Page 35
nstallatIon step onneCtIon ntellIgent rIve odule nstallatIon step ntelligent rive odule 10 a Intelligent-Drive-Module IDM Part.-No.: 688257-9 Part.-No.: 688257 Application: Factory fitted module installed into an Application: Module for the self installation SHEV Control Unit EMB 8000+ and fully wired, for on customer side for operating intelligent A umüller operating intelligent A...
Page 36
onneCtIon ntellIgent rIve odule 10 a Connection: Intelligent-Drive-Module IDM Drive composite system with M-COM Automatic Ventilation configurable 24 V DC in S12 24 V DC in S12 24 V DC in S12 When connecting the drives e.g. re-registration Ventilation control push button maximum power consumption note potential-free contact...
Page 37
nstallatIon step onneCtIon elay odule nstallatIon step elAy odule Relay-Module RM6 Part.-No.: 688200-9 Part.-No.: 688200 Application: Factory fitted module installed into an Application: Module for the self installation on SHEV Control Unit EMB 8000+ and fully wired, for the customer side into the SHEV Control Unit EMB 8000+ transmitting of signals via potential-free relay contacts.
Page 38
onneCtIon elay odule 10 a 24 a 48 a 72 a Connection: Relay-Module RM6 Relay contacts potential-free: e.g. fault, EMERGENCY-OPEN For the use of Contact load: max. 42V, 0,5A Relay-Module RM6 Terminals: max. 1,0 mm is a licensed Software mandatory! Relay 1 Relay 2 Relay 3...
Page 39
nstallatIon step : knx-m im-k onneCtIon odule : knx-m im-k nstallatIon step odule KNX-Module IM-K Part.-No.: 688265-9 Part.-No.: 688265 Application: Factory fitted module installed into Application: Module for the self installation on an SHEV Control Unit EMB 8000+ and fully wired, for customer side into the SHEV Control Unit EMB 8000+ communication between the A Control Unit...
Page 40
: knx-m im-k onneCtIon odule 10 a 24 a 48 a 72 a Connection: KNX-Module IM-K 6x Analogue input for sensors: Relay contacts potential-free: e.g. temperature, CO2, 0-10V, etc. max. 42V, 0,5 A max. 24 V, 0,5 A Relay 1 Relay 2 Relay 3 Operation display (green)
Page 41
nstallatIon step onneCtIon eather odule 9: W nstallatIon step eAhter odule Weather-Module WM Part.-No.: 688180-9 Part.-No.: 688180 Application: Factory fitted module installed into an Application: Module for the self installation on SHEV Control Unit EMB 8000+ and fully wired, for the customer side into the SHEV Control Unit EMB 8000+ connecting of weather sensors.
Page 42
onneCtIon eather odule 10 a 24 a 48 a 72 a Connection: Wind and rain sensor to Weather-Module WM Rain sensor Wind sensor Rain sensor Wind sensor 24 V DC 24 V DC max. 200 m max. 200 m min. 0.5 mm min.
Page 43
nstallatIon step : bus-s bus-b onneCtIon moke eteCtor reak lass nIts 10 a 24 a 48 a 72 a nstallatIon step bus- bus- (hse) smoke detector And breAk glAss units BUS-smoke detector and BUS-break-glass units (HSE) Connect the shielding on one side of the cable with the metal housing! to the next...
Page 44
11: m nstallatIon step odIfy odule onfIguratIons 12: o nstallatIon step PeratIon omPletIng nstallatIon nstallatIon step odify module configurAtions The Control Unit is configured at the factory. All specifications in this The configuration of the Control Unit using the software description refer to standard scope of delivery.
Page 45
ndICator ontrol lements 10 a 24 a 48 a 72 a ndicAtor And ontrol elements Display the operating state Displays: Triggering of Alarm / EMERGENCY-OPEN Icon Importance Icon Importance Display red: Display green: • On module CM / SM / DM / DMX / IDM: Permanently light: Correct conditions Automatic or manual triggering of Blinks:...
Page 46
ndICator ontrol lements 10 a 24 a 48 a 72 a LED display for break-glass unit (HSE) The fuse is located on top of the respective module. The following modules are secured with fuses: Display State Fuse: Power-Module PM Normal operation F1 = 25 A (flat fuse ISO 8820-3) Fault...
Page 47
roubleshootIng ePaIr 10 a 24 a 48 a 72 a roubleshooting And epAir All functions and system components that are important for the The overview below details some of the possible faults and problem SHEVS operation are constantly monitored for faults. A fault indication cases and their causes.
Page 48
roubleshootIng ePaIr 10 a 24 a 48 a 72 a Sensor-Module SM Drive-Module DM (10a) / DMX (20a) / IDM (10a) Triggering of alarm Triggering of alarm Cause / possible solution Cause / possible solution (EMERGENCY-OPEN) (EMERGENCY-OPEN) EMERGENCY-OPEN has triggered Open smoke vents (drives) Displays also valid for external LEDs (break-glass unit) Smoke detector still active after...
Page 49
aIntenanCe AintenAnce And odificAtion mportAnt mAintenAnce informAtion To ensure continuous function and safety of the complete system periodic • While working in the Control Unit the workplace must be secured maintenance by a specialist contractor is required at least once a year against unauthorised access.
Page 50
emountIng IsPosal arranty IabIlIty emounting And dismAntling ArrAnty And ustomer service The Control Unit must be stored only in locations protected from mois- In principle, our: ture, severe contamination and temperature fluctuations (not above „General Terms for the Supply of Products and Services of the 30°C).
Page 51
ertificAte And eclArAtion of onformity The proof of the application of a quality management We declare under our sole responsibility that the product system is for company: described under "Data sheet" is in conformity with the GmbH umüller umatIC following directives: according to the certification basis DIN EN 9001 as well the "Declaration of Incorporation and Conformity"...