Aumuller SHEV EMB 8000+ Series Installation And Commissioning Instructions

Hide thumbs Also See for SHEV EMB 8000+ Series:

Advertisement

Quick Links

Installation and Commissioning
Power supply according to EN12101-10 and Control Unit according to prEN12101-9
SHEV - C
U
ontrol
tested electrical control device EMB 8000+
with recognition number G512005
EMB 8000+ (5A / 10A / 24A / 48A / 72A)
nit
Instructions

Advertisement

loading
Need help?

Need help?

Do you have a question about the SHEV EMB 8000+ Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Aumuller SHEV EMB 8000+ Series

  • Page 1 Installation and Commissioning Instructions Power supply according to EN12101-10 and Control Unit according to prEN12101-9 SHEV - C EMB 8000+ (5A / 10A / 24A / 48A / 72A) ontrol tested electrical control device EMB 8000+ with recognition number G512005...
  • Page 2 ontents Abbreviations Warning and Safety Symbols Target Groups, Intended Use Safety Instructions, Guidelines and Standards 3 - 8 Overview: EMB 8000+ in the installation Overview: EMB 8000+ module 9 - 10 Technical Data Preparing assembly Information regarding equipment and version of Control Unit Arrangement, order and connection of modules on standard rail 11 - 14 Connection: Main power supply...
  • Page 3 refaCe remark bbreviAtions Index of abbreviations Scale units These abbreviations are used consistently throughout this instruction. °C Degree Celsius Unless stated differently, all dimensions indicated in this document are in mm. Amperes General tolerances in accordance with DIN ISO 2768-m. Amp-hours Surface mounting Kilogram...
  • Page 4 refaCe remark Arget group These instructions are intended for personnel trained in This device is not intended for use by per- Arning electrical engineering and skilled operators of systems sons (including children) with physical, for natural smoke ventilation (NRA / SHEV) (natural smo- sensory or mental limitations or lacking experience and / or ke exhaust system / smoke and heat exhaust system) and knowledge, unless they are supervised by a person who is...
  • Page 5 refaCe remark The need for a risk assessment at the installation site • the installation height of the drive and lower edge due to reasonably foreseeable misuse. of casement < 2,5 m above the floor A risk assessment in accordance with the Machinery and one of the following conditions: Directive 2006 / 42 / EG by activation of the power- •...
  • Page 6 afety instruCtions We recommend using exclusively sys- Basic functions of SHEV (smoke and heat exhaust sys- tem components by A , because tem) control devices: umüller their compatibility is carefully checked • Control of electric window drives for smoke in the factory. A shall not assume and heat exhaust in case of fire and for “natural umüller...
  • Page 7 afety instruCtions The power line on-site must be secured se- Other persons must be kept away from parately and provided all poles separators. the casement when a hold-to-run switch After opening of the system housing voltage (push button) is operated or when a Aution carrying parts are exposed.
  • Page 8 afety instruCtions The prerequisites of the system (see chapter “S Declaration of Conformity yStemS Confi ”) must be checked prior to installation. The control device is manufactured and inspected for guration of Software The “Software clause for handing over the standard soft- its intended use in accordance with the European guide- ware as part of shipments”...
  • Page 9 reParing assembly : emb 8000+ vervieW NHXH-FE 180 / E 90 min. 3 x 1,5mm Note: Number depends on the configuration of the modules. JE-H (St) H FE 180 / E 90 external 2 x 2 x 0,8 fire alarm system JE-H (St) H FE 180 / E 90 J-Y (St) Y - 2 x 2 x 0,8 (Button without display) 2 x 2 x 0,8...
  • Page 10 reParing assembly : emb 8000+ m vervieW odule JE-H (St) H FE 180 / E 90 JE-H (St) H FE 180 / E 90 2 x 2 x 0,8 mm, max. 400 m 2 x 2 x 0,8 mm, max. 400 m max.
  • Page 11 reParing assembly 10 a 24 a 48 a 72 a echnicAl Electrical data and connected loads Environmental Conditions (operation) Operating voltage, primary: 195…..253 V AC Ambient temperature range: -5…+40 °C Frequency: 50….60 Hz Maximum relative air (according to EN 12101 Class 1) Current consumption (primary): (depending on version) humidity:...
  • Page 12 reParing assembly 10 A 10 a 24 A 24 a 48 A 48 a 72 A 72 a otes on the ontrol nit equipment And version Determining the right equipment for the Calculating: maximum allowable number of Control Unit modules In order to be able to determine the right version and equipment of In order to guarantee a high degree of adaptability to the variety of structural requirements, the emB 8000+ is designed as a modular...
  • Page 13 reParing assembly 10 a 24 a 48 a 72 a Space requirement for modules Following module requirement as an example Once the required number of modules is determined, their space requi- rement on the standard rail can be easilycalculated with the respective 34,0 module width: The modules‘...
  • Page 14 reParing assembly 10 a 24 a 48 a 72 a rrAngement order And connection of modules on the stAndArd rAil Arrangement and order of modules Connection of modules The modules are mounted on the standard rail directly next to each other. When connecting the modules, one must differentiate between three kinds of connections: Following module arrangement must be absolutely adhered to:...
  • Page 15 nstallatIon step onneCtion ain Power suPPly nstallatIon step onnection Ain poWer supply The max. power consumption per Drive-Modules DM / DMX / IDM, which can be connected to a switching Only connect when disconnected from the mains pow- power supply with PM or PME depends on the respective er supply! Switch off power supply and secure against switching power supply (5 a, 10 a, 24 a).
  • Page 16 nstallatIon step onneCtion ain Power suPPly Connection of main power supply: 10 a 24 a Power-Module pm with one switching power supply 10 a or 24 a Fuse Fuse with 10 a Operation display (green) Operation display (green) 10 a or 24 a Status display (green) Fault display (yellow) Fault display (yellow)
  • Page 17 nstallatIon step onneCtion odules to 10 a 24 a 48 a 72 a nstallatIon step onnection odules to Since we are dealing with a digital BUS, the modules can be intercon- nected with the ribbon cable on the bottom of the module independent Only connect when disconnected from the mains of their function within the system.
  • Page 18 nstallatIon step Can-bus nstallation onneCtion of several ontrol nits via 10 a 24 a 48 a 72 a nstallatIon step cAn-bus nstAllAtion onnection of severAl ontrol nits viA If required, a BUS-compatible fireproof cable must be For this application the system must be configured with used.
  • Page 19 verview of ConneCtion of external ComPonents 10 a 24 a 48 a 72 a vervieW of connection of externAl components Line length and cross-section A (drives) depend on the type of drive and Allowable connection values: on the number of drives. Line length and cross-section can be determined from the following formula: a = display, max.
  • Page 20 verview of ConneCtion of external ComPonents 10 a 24 a 48 a 72 a Connection: Power-Module PM Connection: IM-K max. 0,5 A 24 V DC Indicators´ side In 6 In 5 In 4 In 3 24 V DC In 2 System voltage In 1 (back-up battery cached)
  • Page 21 verview of ConneCtion of external ComPonents 10 a 24 a 48 a 72 a Connection: Drive-Module DM / DMX Connection: Intelligent-Drive-Module IDM DMX = without terminal Drives S12 24 V DC Line end IDM = 10 A module Drives 24 V DC DM = max.
  • Page 22 nstallatIon step onneCtion ower odule xtension nstallatIon step oWer odule xtension Power-Module-Extension PME Part.-No.: 688100 Application: Module for the self installation on customer side into the SHEV Control Unit EMB 8000+ for monitoring of the main power supply. Operating voltage: 24 V DC Internal consumption: 0 mA...
  • Page 23 onneCtion ower odule xtension 10 a 24 a 48 a 72 a Connection: Power-Module-Extension PME from PME 2 PM / PME 1 Operation display (green) Status display (green) next DM(X) Back-up batteries Power supply Installation instruction SHEV - Control Unit EMB 8000+...
  • Page 24 nstallatIon step onneCtion ower odule nstallatIon step oWer odule xtension Power-Module PM Part.-No.: 688050 Application: Module for the self installation on customer side into the SHEV Control Unit EMB 8000+ for monitoring of the main power supply. Operating voltage: 24 V DC Internal consumption: 16,1 mA Housing (WxHxD):...
  • Page 25 onneCtion ower odule 10 a 24 a 48 a 72 a Connection: Power-Module PM System voltage (cached by back-up batteries) max. 0,5 A Voltage (not cached by back-up batteries) Connection to PME 1 The use of back-up battery cached system voltage may demand larger Operation display (green) batteries Status display (green)
  • Page 26 nstallatIon step onneCtion ontrol odule 5: c nstallatIon step ontrol odule Control-Module CM Part.-No.: 688120 Application: Module for the self installation on customer side into the SHEV Control Unit EMB 8000+ for the connecting of automatic smoke detectors and break-glass units. Operating voltage: 24 V DC Detector line voltage:...
  • Page 27 onneCtion ontrol odule 10 a 24 a 48 a 72 a Connection: Control-Module CM Signalling line 1 Signalling line 2 Signalling line 3 Automatic smoke detector or Break-glass unit (manual fire alarm) triggering of external fire alarm unit Resistance R must remain in the last or only detector.
  • Page 28 nstallatIon step onneCtion ensor odule 6: s nstallatIon step ensor odule Sensor-Module SM Part.-No.: 688150-9 Part.-No.: 688150 Application: Factory fitted module installed into an Application: Module for the self installation on SHEV Control Unit EMB 8000+ and fully wired, for the customer side into the SHEV Control Unit EMB 8000+ connecting of automatic smoke detectors and for the connecting of automatic smoke detectors and...
  • Page 29 onneCtion ensor odule 10 a 24 a 48 a 72 a Connection: Sensor-Module SM Signalling line 1 Signalling line 2 Signalling line 3 (manual fire alarm) Break-glass unit Automatic smoke detector or triggering of external fire alarm unit Resistance R E must remain in the last or only detector.
  • Page 30 nstallatIon step onneCtion rive odule nstallatIon step rive odule 10 a Drive-Module DM Part.-No.: 688250-9 Part.-No.: 688250 Application: Factory fitted module installed into an Application: Module for the self installation on SHEV Control Unit EMB 8000+ and fully wired, for the customer side into the SHEV Control Unit EMB 8000+ controlling of drives, gas-pressure generators and mag- for the controlling of drives, gas-pressure generators and...
  • Page 31 onneCtion rive odule 10 a Connection: Drive-Module DM (10a) Automatic Ventilation Drives 24 V DC Ventilation control push button OPEN CLOSE max. max. Stop 400 m 10 pieces configurable Drive line with fixed-temperature heat detector e.g. re-registration CLOSE CLOSE potential-free contact Drive line OPEN OPEN...
  • Page 32 nstallatIon step onneCtion rive odule nstallatIon step rive odule 20 a Drive-Module DMX Part.-No.: 688255-9 Part.-No.: 688255 Application: Factory fitted module installed into an Application: Module for the self installation on SHEV Control Unit EMB 8000+ and fully wired, for the customer side into the SHEV Control Unit EMB 8000+ controlling of drives, gas-pressure generators and mag- for the controlling of drives, gas-pressure generators and...
  • Page 33 onneCtion rive odule 20 a Connection: Drive-Module DMX (20a) Automatic Ventilation Drives 24 V DC Ventilation control push button OPEN CLOSE max. max. Stop 400 m 10 pieces configurable Drive line with fixed-temperature heat detector e.g. re-registration CLOSE CLOSE potential-free contact Drive line OPEN OPEN...
  • Page 34 nstallatIon step onneCtion ntelligent rive odule nstallatIon step ntelligent rive odule 10 a Intelligent-Drive-Module IDM Part.-No.: 688257-9 Part.-No.: 688257 Application: Factory fitted module installed into an Application: Module for the self installation SHEV Control Unit EMB 8000+ and fully wired, for on customer side for operating intelligent A umüller operating intelligent A...
  • Page 35 onneCtion ntelligent rive odule 10 a Connection: Intelligent-Drive-Module IDM Drive composite system with M-COM Automatic Ventilation configurable 24 V DC in S12 24 V DC in S12 24 V DC in S12 When connecting the drives e.g. re-registration Ventilation control push button maximum power consumption note potential-free contact...
  • Page 36 nstallatIon step onneCtion elay odule nstallatIon step elAy odule Relay-Module RM6 Part.-No.: 688200-9 Part.-No.: 688200 Application: Factory fitted module installed into an Application: Module for the self installation on SHEV Control Unit EMB 8000+ and fully wired, for the customer side into the SHEV Control Unit EMB 8000+ transmitting of signals via potential-free relay contacts.
  • Page 37 onneCtion elay odule 10 a 24 a 48 a 72 a Connection: Relay-Module RM6 Relay contacts potential-free: e.g. fault, EMERGENCY-OPEN For the use of Contact load: max. 42V, 0,5A Relay-Module RM6 Terminals: max. 1,0 mm is a licensed Software mandatory! Relay 1 Relay 2 Relay 3...
  • Page 38 nstallatIon step : knx-m IM-K onneCtion odule : knx-m im-k nstallatIon step odule KNX-Module IM-K Part.-No.: 688265-9 Part.-No.: 688265 Application: Factory fitted module installed into Application: Module for the self installation on an SHEV Control Unit EMB 8000+ and fully wired, for customer side into the SHEV Control Unit EMB 8000+ communication between the A Control Unit...
  • Page 39 : knx-m IM-K onneCtion odule 10 a 24 a 48 a 72 a Connection: KNX-Module IM-K 6x Analogue input for sensors: Relay contacts potential-free: e.g. temperature, CO2, 0-10V, etc. max. 42V, 0,5 A max. 24 V, 0,5 A Relay 1 Relay 2 Relay 3 Operation display (green)
  • Page 40 nstallatIon step onneCtion eather odule 9: W nstallatIon step eAhter odule Weather-Module WM Part.-No.: 688180-9 Part.-No.: 688180 Application: Factory fitted module installed into an Application: Module for the self installation on SHEV Control Unit EMB 8000+ and fully wired, for the customer side into the SHEV Control Unit EMB 8000+ connecting of weather sensors.
  • Page 41 onneCtion eather odule 10 a 24 a 48 a 72 a Connection: Wind and rain sensor to Weather-Module WM Rain sensor Wind sensor Rain sensor Wind sensor 24 V DC 24 V DC max. 200 m max. 200 m min. 0.5 mm min.
  • Page 42 nstallatIon step : bus- bus- onneCtion smoke deteCtor and break glass units 10 a 24 a 48 a 72 a nstallatIon step bus- bus- (hse) smoke detector And breAk glAss units BUS-smoke detector and BUS-break-glass units (HSE) Connect the shielding on one side of the cable with the metal housing! to the next...
  • Page 43 11: m nstallatIon step odify module Configurations 12: o nstallatIon step Peration omPleting nstallation 10 a 24 a 48 a 72 a nstallatIon step odify module configurAtions The Control Unit is configured at the factory. All specifications in this The version VIEW limits the system control and configuration to the fol- description refer to standard scope of delivery.
  • Page 44 ndiCator and ontrol elements 10 a 24 a 48 a 72 a ndicAtor And ontrol elements Display the operating state Displays: Triggering of Alarm / EMERGENCY-OPEN Icon Importance Icon Importance Display red: Display green: • On module CM / SM / DM / DMX / IDM: Permanently light: Correct conditions Automatic or manual triggering of Blinks:...
  • Page 45 ndiCator and ontrol elements 10 a 24 a 48 a 72 a LED display for break-glass unit (HSE) The fuse is located on top of the respective module. The following modules are secured with fuses: Display State Fuse: Power-Module PM Normal operation F1 = 25 A (flat fuse ISO 8820-3)
  • Page 46 roubleshooting and ePair 10 a 24 a 48 a 72 a roubleshooting And epAir All functions and system components that are important for the The overview below details some of the possible faults and problem SHEVS operation are constantly monitored for faults. A fault indication cases and their causes.
  • Page 47 roubleshooting and ePair 10 a 24 a 48 a 72 a Sensor-Module SM Drive-Module DM (10a) / DMX (20a) / IDM (10a) Triggering of alarm Triggering of alarm Cause / possible solution Cause / possible solution (EMERGENCY-OPEN) (EMERGENCY-OPEN) EMERGENCY-OPEN has triggered Open smoke vents (drives) Displays also valid for external LEDs (break-glass unit) Smoke detector still active after...
  • Page 48 aintenanCe AintenAnce And odificAtion mportAnt mAintenAnce informAtion To ensure continuous function and safety of the complete system periodic • While working in the Control Unit the workplace must be secured maintenance by a specialist contractor is required at least once a year against unauthorised access.
  • Page 49 emounting isPosal arranty iability emounting And dismAntling ArrAnty And ustomer service The Control Unit must be stored only in locations protected from mois- In principle, our: ture, severe contamination and temperature fluctuations (not above „General Terms for the Supply of Products and Services of the 30°C).
  • Page 50 Installation instruction SHEV - Control Unit EMB 8000+...
  • Page 51 ertificAte And eclArAtion of onformity The proof of the application of a quality management We declare under our sole responsibility that the product system is for company: described under "Data sheet" is in conformity with the GmbH umüller umatIC following directives: according to the certification basis DIN EN 9001 as well the "Declaration of Incorporation and Conformity"...
  • Page 52 9000024701_V0.1_KW30/19...