INSTALLATION AND COMMISSIONING
SKF Enlight Collect gateway
Important safety warnings:
In some countries, the installer must be certified to connect equipment,
such as a gateway, to plant systems.
Make sure that the power is disconnected before the installation begins.
The system power supply must be provided with an appropriately
positioned, clearly labelled full pole isolator or switch that can be used to isolate
and lock-out power from the gateway during installation, maintenance or
modification work. The switch must be labelled "SKF Enlight Collect gateway" or
similar, with clear identification of which gateway, if multiple units are deployed.
The On/Off position must be clearly marked.
The supply scheme should also incorporate suitable fusing or circuit breakers for
the protection of the supply cable being used.
SKF Enlight Collect IMx-1 System
User Manual
Revision A
41 (84)