6 MECHANICAL INSTALLATION

The XV300K regulator must be wall-mounted vertically, in order to guarantee adequate dispersion of heat in the area
of air circulation and prevent obstructions to air flow in the dissipator zone.
XV300K has IP55 grade protection, anyway protect it from corrosive liquids, gas, heat sources and position it
preferably
sheltered from the sun's rays.
Model
Weight
(kG)
XV308K
2,5
XV312K
4
XV320K
4,8
XV328K
7
9
XV340K
XV350K
17
XV360K
18
C* = increase C value of 29mm with polycarbonate operable door.
(1) = hole closed with watertight plug.

7 ELECTRICAL INSTALLATION

Connect the power wires and ground to the appropriate regulator terminals. To avoid dispersion currents, the motor
earth cable must be connected to the appropriate motor terminal ground. We recommend connecting to the machine's
safety circuit any thermal motor protector in order to remove the control power supply and protect the motor with
maximum efficiency. The thermal motor protector may be otherwise connected directly to the I4 control card's terminal.
If the length of the motor cable exceeds 10 m, we suggest using shielded cable. The control load can consist of
1592016130 XV300K EN MASTER r1.1 16.06.2015
Make sure that it does not undergo vibrations.
Dimensions (mm)
Fixed screw
A
B
C*
D
230
165
150
215
230
265
165
215
230
265
230
215
340
270
235
322
340
270
235
322
340
440
235
322
340
440
235
322
(mm)
Cable glands IP68 (Metric)
E
F
Ø
M16
80
/
M4
1+(1)
170
/
M4
1+(1)
170
/
M4
1+(1)
165
/
M5
1+(1)
165
/
M5
1+(1)
340
170
M5
1+(1)
340
170
M5
1+(1)
XV300K
M20
M25
M32
M40
-
2
-
-
1
2
-
-
1
2
-
-
1
-
2
-
1
-
-
2
1
-
-
2
1
-
-
2