Diagnosis - Emerson Dixell XV300K Series Installing And Operating Instructions

Master controller for ac fans
Table of Contents

Advertisement

BAUDRATE
19200 bps
PARITY
none
BIT STOP
TIME OUT MDB
30

15.5 DIAGNOSIS

TOTAL HOURS
02:23
INT. TEMP.
33.2
PHASE MISS.
4
OVERHEATING
2
EXTERNAL
4
PROBE MISS.
4
1592016130 XV300K EN MASTER r1.1 16.06.2015
[MB]
Defines the transmission speed on channel RS-485
Possible modes: 9600bps, 19200bps (Def.), 38400bps
*
[MB]
Defines the type of parity on the serial transmission.
Possibles modes: None (Def.), even, odd
*
[MB]
Defines the parity bit in the serial transmission.
Possible modes: 1=one bit (Def.), 2=two bits
*
Adjuster's maximum time to receive the setting value on Modbus
transmission. Over this time the adjuster locks the outputs and starts the
[IB]
emergency state.
Min. 1
S
Max. 240s
Def. 30s
[DI]
Days and hours of operation of the adjuster
g:h
Caution: in case of reset this value won't be reset
[DI]
Internal temperature of the adjuster represented in Centigrades
°C
[DI]
Quantity of stops due to the missing of a power supply phase or high
disturbances in the power supply line
err
[DI]
Quantity of stops due to the internal overheating
err
[DI]
Quantity of stops due to an external emergency received on the terminal I4
err
[DI]
Quantity of stops due to a breakdown/fault of the possible power supply
probe 4...20 mA
err
XV300K
24/26