Carrier Atmosphera 42EM Series Manual page 9

Ducted fan coil unit
Table of Contents

Advertisement

42EM Atmosphera
Nominal air flow at high speed
Static pressure available at nominal air flow
(unit without supply and return air plenum)
Total cooling capacity - chilled water coil*
Sensible capacity - chilled water coil*
Heating capacity - hot water coil**
Power supply 230 V - 1 ph - 50 Hz
Operating weight (base unit and return air plenum)
Water coil
Copper tubes Ø 3/8"
Aluminium fins, purge valve, female connection
Test pressure
Operating pressure
2-row coil
Connection
Water content
Monobloc 4-row coil
Cooling connection
Heating connection
Water content
-
cooling
-
heating
Electric heater - resistance wire type
Power supply: 230 V - 1 ph - 50 Hz
Heating capacity - excluding fan heat (+5/-10 %)
Self-resetting safety thermostat cut-out temperature
Over-temperature thermofuse link, fusing temperature
Current absorbed
Minimum heater air flow required
Fan
• Number of centrifugal wheels
Motor
Maximum absorbed power at 230 V***
Nominal current***
Starting current
Air filter
Dimensions
Filter efficiency: 85% (gravimetric) - G3
Fresh air connection
Outside diameter
Constant minimum air flow (-10% - +20%)
Constant maximum air flow (-10% - +20%)
∆P (upstream/downstream):
3
- Controller 8.3 l/s (30 m
/h)
- Controller 16.7 to 44.4 l/s (60 to 160 m
Variable air flow (optional motorised valve) - min./max.
Min. available pressure in upstream fresh air duct
(motorised valve)
Atmosphera water connections
The water circuit in the Atmosphera units is guaranteed for an operating pressure of 1000 kPa, although the Atmosphera units components are individually
designed and tested for a pressure of 1600 kPa.
For applications requiring an operating pressure of more than 1000 kPa, please contact your local Carrier representative.
Legend:
*
Based on an entering water temperature of 7°C, entering air at 27°C dry bulb and 47% relative humidity, and a water temperature difference of 5 K at maximum
air flow (Eurovent conditions).
**
Based on an entering water temperature of 50°C, entering air at 20°C and a water temperature difference of 10 K at maximum air flow (Eurovent conditions).
***
Refer to electrical data tables.
3
l/s (m
/h)
Pa
kW
kW
kW
U %
kg
kPa
kPa
l
l
l
U %
W
°C
°C
A
l/s (m
3
/h)
W
A
A
mm
mm
3
l/s (m
/h)
3
l/s (m
/h)
Pa
3
/h adjustable)
Pa
3
l/s (m
/h)
Pa
Size 3.0
Size 3.1
192 (690)
182 (655)
50
50
5.62
5.31
3.94
3.75
2.05
1.97
± 15
± 15
64+10
66+10
2400
2400
1600
1600
1/2" nut (gas)
3.4
3.4
1/2" nut (gas)
1/2" nut (gas)
3.4
3.4
0.45
0.45
± 15
± 15
1000
1000
75
75
170
170
4.35
4.35
42 (150)
42 (150)
Forward-curved centrifugal fan
2
2
Supply voltage 230 V - 1 ph - 50 Hz, 4 pole asynchronous, internal overload protection,
permanent capacitor, class B winding insulation, varnish class F
110
128
0.52
0.60
1.4
3.0
Throwaway, fire rating medium: M1
208 x 978
208 x 978
125
125
8.3 (30)
8.3 (30)
44.4 (160)
44.4 (160)
50-200
50-200
70-200
70-200
0/55 (0/200)
0/55 (0/200)
180
180
Size 3.2
Size 3.3
272 (980)
325 (1170)
50
50
7.54
8.64
5.38
6.29
2.69
3.07
± 15
± 15
66+10
66+10
2400
2400
1600
1600
3.4
3.4
3.4
3.4
0.45
0.45
± 15
± 15
2000
2000
75
75
170
170
8.7
8.7
55 (200)
55 (200)
2
2
182
229
0.82
1.02
3.0
3.0
208 x 978
208 x 978
125
125
8.3 (30)
8.3 (30)
44.4 (160)
44.4 (160)
50-200
50-200
70-200
70-200
0/55 (0/200)
0/55 (0/200)
180
180
9

Advertisement

Table of Contents
loading