Page 1
CPS_CPS 10 User manual System Part Number: NPCPSGB Revision: J.2 The Fixed Gas Detection Experts...
Page 2
Copyright 2018 by OLDHAM June 2018 All rights reserved. Reproduction in any form, in whole or in part, without the express written consent of OLDHAM is strictly prohibited. The information contained within this manual is true and correct to the best of our knowledge.
Page 3
OLDHAM , even if it is involved in the sale of OLDHAM products. * OLDHAM cannot be held responsible for direct or indirect damage or be required to pay direct or indirect compensation resulting from the sale or use of any of its products IF THESE PRODUCTS HAVE NOT BEEN DEFINED AND CHOSEN BY OLDHAM FOR THEIR SPECIFIC USE.
Page 4
Should questions arise, please contact OLDHAM for additional information. This manual is designed to provide users with simple and precise information. OLDHAM shall is not responsible or liable for any misinterpretation that may result from the reading of this manual.
Page 5
(sulfur dioxide, hydrogen sulfide) • halogenated compounds (R134a, HFO, etc.) • organo-phosphorus compounds (e.g. herbicides, insecticides, and phosphate esters in fireproof hydraulic fluids Oldham recommends regular testing of fixed gas detection installations (read Chapter 6). Page 5 CPS – User Manual...
Table of Contents Chapter 1 Overview of the CPS System ..........8 The CPS central controller ......................10 Digital addressable modules ....................... 10 Digital linking ..........................11 The COM_CPS software application ..................12 System Architecture ........................13 Chapter 2 Assembly / Installation............. 14 Installation of the CPS central controller ................
Page 7
Analog Outputs Module ......................33 Chapter 5 Detailed Menus ..............36 Menu Tree ..........................36 Start-up Phase .......................... 37 Control Menu ..........................38 Normal Display ........................... 38 Sensor Display ..........................38 Events ............................39 Relay Status ..........................39 4-20 mA Output Status ....................... 39 Printing............................
Chapter 1 Overview of the CPS System The system consists of: ▪ a central controller for collecting readings and managing alarms; ▪ various addressable digital modules (sensor modules, relay modules, analog output modules, logic input modules); ▪ instruments and accessories to process alarms and actions The CPS system can manage the detection of 10 different gases, and all detectors are clearly localized and identified.
Page 9
OPENED KLAXON CLOSED Recorder Supervision OPENED OPENED CLOSED CLOSED Speed OPENED CLOSED OPENED CLOSED OPENED OPENED CLOSED CLOSED CPS – User Manual Page 9...
The CPS central controller CPS : Rack mounted 19’’ 4U CPS : Wall mounted version The central controller is available in a 19” 4U (rack-mount) version or in a wall-mount version. It is designed to control: ▪ 256 digital modules distributed over 8 lines, with a maximum of 32 modules per line; ▪...
Digital linking Modules are linked in-line via an MPI 22 or equivalent RS-485 double twisted pair cable, at least 0.22 mm² in diameter. One pair supplies power to the module, the second pair is used for the digital RS-485 link. ISC –...
_CPS software application The COM_CPS software application is designed to help configure the CPS central measuring controller on a PC. COM_CPS software operations are addressed in a separate manual. System and Hardware Requirements: COM_CPS must be installed on a PC running Windows 2000 or Windows XP. The minimum requirements to install COM_CPS are: Windows 98 SE, Windows NT, Windows 2000, Windows XP with 256 MB RAM, Windows VISTA.
System Architecture Rack mounted Control unit CPS SUPERVISION Integrated printer (option) only for rack Mounted CPS COM_CPS configuration Centrale CPS Recorder Serial Printer 8 available digital RS485 Lines 32 addressable modules max per line 256 modules per central CPS Analog output CPS AO4 Detector module CPS 10...
Chapter 2 Assembly / Installation Installation of the CPS central controller The CPS central controller should be installed in a dry, climate-controlled area protected from explosive gases and dust. Ideally, the station should be located in a secure, accessible location under surveillance (security office, control room, equipment room ...).
Installing digital modules Mounting the CPS 10 sensor module Mount the sensor modules on a flat surface using two screws (Fig. 1). The modules should be placed in an accessible area, so that maintenance and inspection operations can be conducted as easily and as safely as possible. Nothing in the area should prevent the sensors from obtaining measurements of the ambient environment.
Central controller electrical connections Electrical connections are wired through the central controller MOTHERBOARD and the power supply 24V. For the CPS central controller (wall-mounted version), you must open the casing door to access the electrical panel. Electrical connections must be done by a qualified professional. Observe all current Directives, notably the European Low Voltage Directive.
Page 18
MOTHERBOARD FOR RACK-VERSION CPS Fig. 3 : POWER SUPPLY 24 VDC 0V +24 VDC 24 VCC Fig. 4 : 110- power supply 240VCA Bus 1 Bus 3 Bus 5 Bus 7 Bus 8 Bus 2 Bus 4 Bus 6 +Def Fig.
Overview of the Motherboard Part Connector function Part Connector function Digital addressable modules 110-240VCA main power supply (rack 8 line connectors for connecting digital modules version) (CPS 10 – CPSRM – CPSDI16 – CPSAO4) 24 VDC external power supply connection RS-485 digital output 110-240VCA power supply for (wall- links to a supervision system...
Inspecting the digital buses Bicolor (red/green) LEDs located above each line start, on the motherboard, allows for inspection of the bus links as follows LED appearance Status Communication DEL of the bus Red + Green LEDs lit (LEDs Normal operation. blink rapidly, almost Red LED...
USB / RS-232 serial connectors The CPS central controller is equipped with a serial port which are used to: download the user software (see COM_CPS instructions); program the integrated micro application according to the position of mini switches on the board (factory setting).
Printer (Optional feature) Connection: Central controller RS-232 interface via an RS-232 serial cable. Communication settings: 19200 Bd, 8 bit, no parity. Event printing “on the fly.” Status table printing (choice of four printing schedules). For example: average readings over 20 minutes, 1 hour, or 8 hours, summary of alarm and relay statuses.
The front panel circuit ☺ a b c d e f g h i j k l m n o p q r s t u v w x y z 0 1 2 3 4 5 The central controller front panel circuit is A B C D E F G H I J K L M N O P Q R S T U V W X Y Z 0 1 2 3 4 5 equipped with:...
Alarm thresholds Six alarm thresholds can be programmed and adjusted for each sensor: Alarm 1, Alarm 2, Alarm 3, Alarm 4, Out of Range and Fault. Alarms 1 – 4 can be: Instantaneous; delayed (0 to 3,600 seconds); averaged (period of 1 to 480 minutes). This makes it possible to calculate STEL and TWA values.
Connecting Digital Modules General topology of the RS-485 network Modules are connected in “parallel” in the RS-485 network, comprised of a 1 twisted pair cable for signals, 1 or more pairs to supply power to the modules, and 1 shield wire. A 120 end of line resistor (EOL RESISTOR) should be placed at the last module in the line, at the end of the bus (see Chapter 4 - End of Line Resistor).
Configuring the communication settings Slave address Fig. 10 : CONFIGURATION SWITCH All modules in a line should be identified with a unique slave number. Switches 1-5 on the unit (Fig. Configuration Switches 10) contained in each module, allow you to set a binary numerical address (1…32).
CPS 10 Detector Module The CPS central controller accepts 10 types (or 10 different configurations) of sensors. The type of sensor used in the module depends on the gas being monitored. Electrochemical sensors are used to measure CO, NO, NO , for example, while catalytic sensors measure gases such as GPL, CH , and Available Detector Types...
External relay module The relay module is available in two versions: CPS RM4 (with 4 relays) and CPS RM8 (with 8 relays). It also has two logic inputs (LI) which can be activated. In maximum configuration, the CPS can manage 256 relays (ex: 32 modules with 8 relays each). For more information about the logic inputs: see: Logic inputs module.
Relay configuration COM_CPS “Normal” relays The relay is activated when an alarm occurs and is deactivated when the alarm condition ends. The variables acting on a relay in alarm status are: Alarm delay Automatic / Manual acknowledgement Forced state change via the CPS menu Forced state change via a logic input command “Buzzer”...
Page 32
“LS / HS” Operation < Requirements: Alarm level 1 Alarm level 2 The LS relay is activated by Alarm 1 The HS relay is activated by Alarm 2 Default Phases Action operation Delay* Min. duration LS operation Minimum duration, in seconds, during which the 5 min.
Logic Input Module This module contains 16 logic inputs, linking priority commands, such as fire COM_CPS extinguishers directly to the central controller. A maximum of 224 total logic inputs across all modules can be activated. Example 1: 112 modules having 8 relays each, with activated inputs. Example 2: 7 modules with 16 logic inputs with activated inputs.
Page 34
Connections: Analog Example of use with analog output module output Analog output module module Logic input EL1 and EL2 ( IN1 and IN2) OUTPUT 4-20 mA from channel 1 to 3 Module power supply and digital liaison ( A and B) Output 4-20 mA from the channel 4 Page 34 CPS –...
Chapter 5 Detailed Menus Menu Tree ☺ a b c d e f g h i j k l m n o p q r s t u v w x y z 0 1 2 3 4 5 A B C D E F G H I J K L M N O P Q R S T U V W X Y Z 0 1 2 3 4 5 Start Display Events...
Start-up Phase No faults or alarms are processed during the first ☺ minute after start-up. During this phase, the central controller runs a Checksum test (1), a Checksum RAM test (2), a line start-up (3) and a module mapping test with a program stored in its memory.
Control Menu ☺ Normal Display Control 1 3 : 1 8 : 1 9 Alarm pictograms will appear and disappear in along with the alarm conditions detected by a given sensor. The display shows gas level readings, which may not always be identical to the ☺...
Events This menu can be used to search through a history of the most recent 1,200 events. A record of these events can be printed. State changes are recorded in the history. If Alarm 1 ends and Alarm 2 is triggered, AL2 ON will be recorded. Examples: (a) The shut-down of a line causes the shut-down of alarms and relays for that line.
Printing “System status” Report This menu is used to initiate the printing of system ☺ status reports. The second part indicates the fault status for all of the modules in each line. Each Control hexadecimal number corresponds to a module, 13: 52: 17 with Module 1 being on the left, and Module 32 on the right.
☺ System Menu System 17: 23: 17 Line, Module, Relay Action [ ] [ ] Enter the access code by using the ☺ [ ] [ ] keys System Line activation Activation line, module, relay ...
☺ Activating analog outputs Choose the 4-20 mA output for the selected Output 4 – 20 mA module. Pressing [ OK ] will force a start-up or shut-down for the 4-20 mA output. The shut-down freezes the output at 4 mA. The start-up freezes the output at 20 mA.
Maintenance Menu ☺ Simulation Maintenance 09: 52: 15 This menu is used to simulate the alarms for a particular sensor module or to temporarily activate ☺ one or more relays (or outputs). After exiting the simulation menu, the sensors and relays Maintenance (excluding LS and HS relays) revert to their prior Simulation...
Module Verification ☺ Inspection of all of the parameters relating to a module with a communication fault. Maintenance Module Control ☺ Line : Module: CPS 10 niveau-1 E = Status word D = Fault word C = Start-up config. word ☺...
Page 45
Any module fault generates an event, which is identified by a number (hexadecimal coding) corresponding to the fault type. The number at the end of the second line displays the module error. [ ] keys can be used to change the scroll mode : in normal mode, all events saved to memory are displayed;...
Bus Faults This menu displays the faults from all modules in ☺ a line. Each hexadecimal number corresponds to a module, with Module 1 being on the left, and Maintenance Module 32 on the right. default 0 = OK 1 = Communication error ☺...
Chapter 6 Maintenance Program transfer This chapter describes the transfer of data from the COM_CPS application to the CPS, and vice versa (see the COM_CPS user’s guide). After launching the software, you will see a welcome window. PC CPS transfer Once the program has been created, the central controller should receive new settings..
Error messages Error messages will appear in the following scenarios: ERR 01: Module fault relating to the program. The test runs systematically on start-up and periodically when a module is activated by the menu if the module does not correspond to the loaded program. The error remains until the problem is corrected or until the module is shut down.
Warning :The setting of this section are reserved for authorized persons formed because they might call into question the reliability of detection. The site responsible is required to establish security procedures on its site. OLDHAM may be not responsible for their implementation.
Semi-automatic calibration During a sensor module calibration, the central controller blocks the alarms from the module in question and displays a maintenance key on the screen. Up to 10 sensors can be calibrated at the same time. The concentration level for the calibration gas is stored in the sensor’s memory. Each calibration start and stop is logged as an event.
Manual calibration The calibration kit provided by ISC must be used (Ref. 6 116 291) female connector / wires / voltmeter connection files). Remove the sensor cover. Connect the cable (strand) to the circuit’s male connector. Zero adjustment Ensure that the sensor is in clean air. If not, inject air into the sensor at a flow rate of 60 l/h, then wait for voltmeter levels to stabilize (use the gas injection device: bottle of synthetic air, calibration pipe, tube).
Semi-automatic calibration device Calibration LED Magnet position. Respect the magnet position in order to place the magnet horizontally Semi-automatic calibration The magnetic calibration allows for one-man and non-intrusive calibration to save considerable time. Manual calibration with zero and span potentiometers is possible by opening the CPS 10 Calibration element Slug the gas...
Central controller maintenance Do not use alcohol- or ammonia-based liquids to clean the central controller. If necessary, clean the exterior of the central controller with a damp cloth. Lithium battery If the central controller configuration settings are lost, the lithium battery soldered to the display card must be replaced.
CPS 10 Sensor Module Dimensions (mm): 118 x 110 x 60 Degree of protection: IP 65 Cable entries: 2 M16 cable glands 4-8 mm diameter Consumption: Toxic gas sensor: 2.5 mA in normal operation Explo gas sensor: 50 mA in normal operation Status indication after calibration Red/Green electroluminescent diode Calibration:...
Need help?
Do you have a question about the CPS Series and is the answer not in the manual?
Questions and answers