Honeywell VARIODYN D1 Installation Instruction page 68

Table of Contents

Advertisement

Installation Instruction VARIODYN
7.4.6 DIP switch 4XD300/4XD500
Before commissioning, the DIP switch
ON corresponds to the upper position and OFF to the lower one.
Disconnect the amplifier from the power source before setting the DIP switch
Set the DIP switch using a non-metallic tool.
The DIP switch positions are read in when booting up the amplifier.
- 20 dB
- 6 dB
1 2 3 4 5 6
CH 1
2
3
4 DC
LOOP
FAULT
SHORT DETECT
- 20 dB
- 6 dB
1 2 3 4 5 6
CH 1
2
3
4 DC
LOOP
FAULT
SHORT DETECT
- 20 dB
- 6 dB
1 2 3 4 5 6
CH 1
2
3
4 DC
LOOP
FAULT
SHORT DETECT
Loop mode is only permitted for operation using loop technology incl. loop isolator modules (LIM).
68
®
D1 System
5
should be set to the desired function according to the table below. Here,
ON:
Signal LED 'sensitivity' illuminates from -20 dB for each channel
ON
CH 1...4.
OFF
OFF:
Signal LED 'sensitivity' illuminates from -6 dB for each channel
CH 1...4.
ON:
Faults relating to the 24 V power supply (AC and DC) are
ON
displayed.
OFF
OFF:
Faults relating to the 230 V power supply (AC only) are
displayed.
ON:
Loop mode
ON
In the event of a short-circuit, the amplifier switches off for
approximately 0.75 seconds before restarting again immediately
OFF
at full power. This means the loop is fully available again more
quickly following a short-circuit.
OFF:
Normal mode/spur line
In the event of a short-circuit, the amplifier switches off for
approx. five seconds. The power is then slowly increased again
after this.
5
.
FB 798663.GB0 / 05.19