Features
Approved in accordance with EN 54-17 (included in the EN 54-16 approval of the VARIODYN
Up to 4 rings per DOM4-8 or DOM4-24
Up to 500 W power per loop
Up to 5 spurs with more than one loudspeaker per loop (including EOL)
Easy migration of existing spurs into the loop
Fully fail-safe if each loudspeaker is fitted with an LIM
Replaces A/B cabling
Partially eliminates the need for E 30 cabling (DIN VDE 0833-4, chapter 7.10)
Various standard cable types can be used for loudspeakers
Cable leads can be wired in parallel to increase the cable cross-section - Do not route outbound and inbound
loop conductors in the same cable or the same conduit
Amplifier
2XD250
2XD400
4XD250B
4XD300
4XD500
No other amplifiers are approved for combination with LIMs
Observe the maximum number of LIMs and the loop length for the amplifier used
20 % power reserve per amplifier should be planned in
The maximum load is different for each amplifier and should be determined in consultation with
the Technical Support.
Three operating modes can be implemented with a DOM4-8 or DOM4-24:
Fig. 14: Operation with
up to 4 loop
FB 798663.GB0 / 05.19
Maximum number of LIMs
40
64
25
40
50
Fig. 15: Operation with
up to 8 spurs
Installation Instruction VARIODYN
Max loop length including spur lines
Fig. 16: Mixed operation, e.g. with 2 loops
and 4 spurs (example)
®
D1 System
®
D1 System)
1000
1000
500
1000
1000