7.3.1 Specification - 2XH and 2XD-Series
Type
Mains voltage
Frequency range
Emergency power supply
Rated current @ 230 V AC
Rated current @ 24 V DC
Current (1 kHz sinus / 1 min.)
*7
@ 24 V DC
*8
Output power
Technology
Transmission range
Input level
System input impedance
Signal to noise ratio
Channel separation
Distortion factor @ 1 kHz
Efficiency
Ambient temperature
Storage temperature
Humidity
Housing
Colour
Weight
Dimensions (W x H x D)
Specification
*6
Rated current @ 33% load
*7
Acc. EN 54-16 (laboratory test)
*8
Output power acc. EN 54-16
For analogue amplifiers, the output power is generally used as the planning dimension.
This is not always possible for digital final stages. If there are no details relating to amplifier /
loudspeaker pairings for specific signals, a maximum of 50% of the nominal power should be used as
the planning dimension.
62
®
D1 System
:
:
:
*6
:
*6
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
483 x 88 x 382 mm (2 HU)
:
2XH500
230 V AC, +10% / -15%
50 ... 60 Hz
24 V DC
5,7 A
41 A
86,0 A
2 x 500 W
class H
20 ... 22 kHz
0 dBu
≥ 10 kOhm
≥ 101 dB
≥ 75 dB
≤ 0.05 %
approx. 50 %
-5 °C ... +55 °C
-10 °C ... +60 °C
40 % ... 90 % rel. hum. (non-condensing)
metal
grey, similar to RAL 7016
approx. 17 kg
EN 54-16
2XD250 / 2XD400
1 A / 1,6 A
8,8 A / 13,9 A
25,0 A / 40,5 A
2 x 250 W / 2 x 400 W
class D
50 ... 22 kHz
20 kOhm
≥ 90 dB
≤ 0.3%
≥ 80%
approx. 16,5 kg / 19 kg
483 x 88 x 402 mm (2 HU)
FB 798663.GB0 / 05.19