6.3.1 Protection against a break in the neutral wire
The neutral conductor monitoring module (Part No. 584970) should be used to protect against a break in the
neutral conductor occurring. This module is connected upstream with the MSU contactor (Part No. 584971) and
enables the safe and immediate all-pole interruption of the power supply in the event of:
undervoltage
phase failure
asymmetry, including for reverse voltage
neutral conductor missing in the system
neutral conductor break in the device supply cable
neutral conductor mixed up with phase
The control panels must only be connected to the mains by qualified electricians and in compliance with all
relevant standards and guidelines.