Technical Data - oventrop OV-DMC 3 Operating Instructions Manual

Measuring system with wlan function
Table of Contents

Advertisement

Available languages

Available languages

"OV-DMC 3"
(1)
WLAN / Wi-Fi
- RED (flashing)
- MAGENTA
(flashing)
- MAGENTA
(continuously
illuminated)
- BLUE (continu-
ously illumi-
nated)
(2)
WSN
(3)
On/Off
- GREEN
- WHITE

3.3 Technical data

"OV-DMC 3"
Media temp.
-20 °C to +120 °C
Ambient temp.
0 °C to +40 °C
Storage temp.
-20 °C to +55 °C
Operating pres-
max. 25 bar (2500 kPa)
sure
Differential pres-
max. 2.5 bar (250 kPa)
sure
Measuring range
-20 °C to +120 °C
106927880-V02.03.2019
The appliance is
starting
The appliance is
ready to us as an
access point
The appliance is
connected to a
client as an access
point
This function is not
yet available for
this model
f Check to see
whether new
firmware is
available for
installation
using the app.
This function is not
yet available for
this model
f Check to see
whether new
firmware is
available for
installation
using the app.
The appliance is
switched on
The appliance is
changing mode
Technical description
Air humidity
max. 90 % RH
Temperature
PT 1000
sensor type
Power supply
LiFe battery or using
enclosed USB power
supply unit.
Operating volt-
5 V DC
age
Power consump-
500 mA
tion
Protection class
IP64
Interface
WLAN / Wi-Fi
Radio frequency
2.4 GHz
Transmission
Max. 10 mW
power
Range inside
Dependent on materials
buildings
and sources of interfer-
ence
Media
Water and suitable
water-glycol mixtures
in accordance with
VDI 2035/ÖNORM 5195
Not suitable for steam,
media containing oil, or
aggressive media
Materials
Plastic with brass
connection couplings
and measurement
adapter
Dimensions
Measuring case
with accessories:
370 x 295 x 170 mm
(L x W x H)
Measuring sensor:
107 x 165 x 40 mm
Weight
Measuring case with
accessories: 4300 g
Measuring sensor: 650g
Power supply unit
Type
Friwo FW8002USB/05
Input
100-240 V ~/50-60 Hz/
160-80 mA
Output
5 V
EN
/1400 mA
25