SECTIO N 1 3-RMS-9
99 -
FIG.
PROGRAMMER SECONDARY
CONNECTOR EPIC MICROVERSATRIP®
1 3. 1 .2 RMS-9 & EPIC MICROVERSATRI P ®
INSTALLATION
The program mer mounts to the upper left of the breaker
as shown in Fig. 1 00. It mounts to the bracket assem b ly
shown in Fig. 82. Referring to Fig. 82 , the guid e p ins mate
with the hole on either side of the programmer connector.
They provide the n ecessary alignment for the connector
engagement. The locking lever engages with the pin wh ich
is assem b led to the programmer frame and secures the
program mer to the mounting bracket.
I nstallation .is as follows:
a. I nsert the guide pins into the holes and p ush on the
programmer, engaging the connectors.
b. Th e locking lever is released , securing the program­
mer.
c. Verify that the locking lever did engage the program­
mer pin.
To remove the program mer:
a. Pull out locking lever, which will release the program­
mer pin. Remove the programmer.
&
Epic MicroVersaTrip® (Cont . )
1 3.2 CURRENT SENSORS
nec essary to o p erate the tri p system .
M icroVersaTrip"' , the RMS-9 and Epic MicroVersaTri p '
uses a phase and neutral sensor. Fig. 1 0 1 shows the
phase sensors. See Section 1 3 .5 for cabling d iagrams.
their windings. Their COM MON terminal is the right hand
termi nal as shown in Fig. 1 0 1 . A white wire with a terminal
will be con nected to this COMMON term inal. All phase
sensors must be correctly wired for the programmer
summing circuit to function properly.
wi nding. This winding is brought out to separate flag
terminals. These phase sensors are used when the hi­
level instantaneous RMS-9 option (
Fig. 1 0 2 shows an ' H ' -option phase sensor. When the
' H ' -option phase sensor is i nstalled , there are four leads
connected to it. There is no polarity associated with the
special winding connection . Fig . 1 0 2 shows the connec­
tions for the additional ' H ' -option windings.
The current sensors supply the power and signal i n put
FIG. 1 00 - AKR-70-30
The fixed phase sensors have a polarity associated with
The phase sensors are available with an additional
L i k e the
'
H '-option) is required .
71