FIG. 1 01 - RMS-9 PHASE SENSORS
FIG. 1 02 - ' H'-OPTION PHASE SENSOR
FIG. 1 03 - TYPICAL N EUTRAL SENSOR
Fig. 1 03 shows the neutral sensor. The neutral sensor
is required when integral ground fault protection is used
on single phase-three wire or three phase-four wire sys­
tems. It is inserted into the neutral conductor and therefore
is separately mounted in the cable or bus com partment.
The outputs of the phase sensors and neutral sensor
are connected to a programmer circuit which sums these
values. The total val ue will remain zero as long as there is
no ground current flowi ng. See cable diagram in Fig. 1 07.
The neutral sensor is an electrical dupl icate of the phase
sensor. Therefore, when phase sensors are charged the
neutral sensor must be correspondingly changed .
73