Download Print this page
NARVI MIRVA Series Installation, Use And Service Instructions

NARVI MIRVA Series Installation, Use And Service Instructions

Sauna woodburning stoves

Advertisement

Quick Links

INSTALLATION, USE AND SERVICE
GB
INSTRUCTIONS
SAUNA WOODBURNING STOVES
– MIRVA, STEAMMASTER, NARVI 30 AND NARVI 50.
SAFETY DISTANCES
Prior to installation of the sauna woodburning stove, ensure the required safety
distances to combustible structures are observed. For woodburning stoves the safety
distances are 500 mm to the sides and rear and 1,200 mm overhead. A min. 70 mm
thick concrete slab or a NARVI installation base should be installed beneath the
woodburning stove. For any further queries regarding fire safety, please contact your
local fire authority for assistance.
Note! If the sauna woodburning stove is installed above under-floor heating,
a NARVI installation base must always be used.
Combustible components
(wooden walls, benches etc.)
1. Distance to wooden components from vertical
sides of sauna woodburning stove without heat
shield min. 500 mm. (Figure 1)
2. The safety distance stated in section 1
(500 mm) can be reduced by half to 250 mm if
so-called light, single-layer thermal protection
is installed. A single-layer, light thermal shield
can be made from min. 7 mm thick fire-resistant
fibre-reinforced cement board or from min. 1 mm
thick metal sheet which has been fixed
sufficiently tightly to the wall. A ventilation gap of
30 mm must be left between the thermal shield
and the wooden surface, e.g. using pipe sleeves.
(Figure 2)
The heat shield must also be in non-contact
with the floor or ceiling.
3. The safety distance mentioned in section 2
can be further reduced by half (125 mm) if a
double shield is installed. A double thermal
shield can consist e.g. of two boards of the type
recommended in section 2 if a ventilation gap of
30 mm is left between the wall and the boards.
(Figure 3)
Figure 1
30 mm ventilation gap
1 mm metal plate or 7 mm
incombustible fibre-reinforced
cement board
Figure 2
30 mm ventilation gap
1 mm metal plate or 7 mm
incombustible fibre-reinforced
cement board
Figure 3

Advertisement

loading

Summary of Contents for NARVI MIRVA Series

  • Page 1 500 mm to the sides and rear and 1,200 mm overhead. A min. 70 mm thick concrete slab or a NARVI installation base should be installed beneath the woodburning stove. For any further queries regarding fire safety, please contact your local fire authority for assistance.
  • Page 2 4. If the wall is a masonry wall, a 50 mm ventilation gap between the vertical sides of the sauna woodburning stove and the wall is sufficient. (Figure 4) Measurement A is applied to wooden surfaces in accordance with the thermal protection method applied: Figure 4 - no thermal protection: 500 mm...
  • Page 3 The tunnel model is connected to the flue from the top of the sauna woodburning stove. Always use NARVI chimney pipes or NARVI chimney flues. In connection with the sauna woodburning stove installation, ensure that the woodburning stove stands firmly on its base and that all of the safety distances mentioned in these instructions have been observed correctly.
  • Page 4 Initial heating can also be performed outdoors. SAUNA WOODBURNING STOVE STONES We recommend use of NARVI olivine diabase stones. Stack the stones in the stone compartment so that the biggest stones are at the bottom. In order to ensure good air circulation between the stones, do not stack the stones too tightly.

This manual is also suitable for:

Steammaster series30 series50 seriesMirva stSteammaster wt30 st ... Show all