ABB ControlMaster CM10 Commissioning Instructions page 23

Universal process controller, 1/8 din
Hide thumbs Also See for ControlMaster CM10:
Table of Contents

Advertisement

C O N T R O L M A S T E R C M 1 0  |  U N I V E R S A L   P R O C E S S  C O N T R O L L E R ,   1/8  D I N   |  C I/C M 1 0 - E N   R E V.   C
Icon
Number/
Possible cause
Message
Abnormal oscillations in the control loop.
086.036
Oscillation 1
Motorized valve travel time is significantly
094.034
slower than configured time.
Valve 1
Sticking
Autotune is in progress.
168.026
(166.027)
(164.028)
Tuner 1
Phase 1..3
162.029
Autotune has completed successfully and
(154.033)
calculated new control parameters.
Tuner 1 Pass
The device is currently in the configuration
178.025
mode.
In
Configuration
Suggested action
Check process.
Perform new manual or Autotune.
Check valve to identify reason for sticking.
Check correct travel time is entered in configuration.
Autotune can be aborted if required by selecting Manual control
mode.
Acknowledge diagnostic.
This is for use with remote access via digital communications.
23