INTRODUCTION Thank you for choosing a Tate Airflow product. Tate Airflow products are engineered to maximize the efficiency of your data center air handling system. We would be interested in hearing any comments you may have on this installation manual, product, or overall experience. Please call or e-mail our Technical Service...
Page 4
Pour tous les travaux sur les unités ne peut être réalisée par un professionnel qualifié. Modification des équipements autres que de façon proposés et approuvés par Tate sont ni recommandé ni supporté et peut endommager l'équipement ou causer un préjudice.
Manual Philips Head Screw Driver ADDITIONAL NOTES It is recommended for installations with multiple SmartAire MZ units the MAC Address label (on side of unit) and physical installation location is recorded during unpacking and installation. This will assist in later coordinating the unit through the network connection.
INITIAL SETUP STEP 1: PREPARE THE JOB SITE Mounting hardware not included in SmartAire MZ kit. Must be ordered separately. Please ensure the installment site is clean and free of obstructions. Unpack unit and all accessories. Prepare zip ties and associated mounting hardware available nearby.
Lastly, Install the DirectAire Panel gently into the floor. The DirectAire should rest just above the SmartAire and not apply any force to the SmartAire. If this is not the case please contact Tate for assistance, you may have non-standard understructure.
“Towards” the rack For SmartAire/DirectAire Place the DirectAire panel directly on top of the preinstalled SmartAire MZ on hangers. The DirectAire should rest just above the SmartAire and not apply any force to the SmartAire. If this is not the case please contact Tate for assistance, you may have non-standard understructure.
2. New and untested variations should only be modified in a non-active, controlled manner. MODIFYING ADVANCED MENU OPTIONS MAY SIGNIFICANTLY ALTER THE FUNCTION OF THE SMARTAIRE UNIT, TATE DOES NOT RECOMMEND MODIFYING VALUES WITHIN THE ADVANCED PROGRAMMING ON UNITS WHICH ARE ACTIVELY COOLING EQUIPMENT.
Page 19
If everything is properly connected 1 or more “SMARTAIREMZ” should appear within the window, each with a specific IP and MAC Address. Each line represents one SmartAire unit. Note that SmartAire MZ requires connection to a dynamic DHCP network.
Page 20
Overview: A list of variables which can be configured as listed in the following table. b. TCP/IP Upgrade: To upgrade the system firmware; this is unnecessary to utilize unless directed by Tate. Uploading custom files may cause damage or harm to the SmartAire.
SNMP monitoring points are available for download in a .mib file within the zip file on the right hand “Technical Documents” menu at the following link: http://tateairflow.com/data-center-products/airflow-controls/smartaire-mz The following table of available OID addresses are configured for the SmartAire MZ: Parmeter Label Address Label...
Tate Technical support for warranty terms and support. Alarm Index Note: All alarm conditions will cause SmartAire MZ to react by sounding an alarm, opening all zones fully and re-enabling any disabled zones. Additionally, if configured, an alarm email will processed and sent. Alarm...