Precautions for Wiring
• Use a twisted-pair cable to connect the L
parallel with or near power lines, output lines, and motor lines. Keep the network cable away from noise sources.
• Power down the L
W
ON
the L
W
interface module.
ON
ORKS
• One or two cables can be connected to one terminal of the network interface connec-
tor. When connecting one cable, use AWG24 to AWG14 cables (core cross-section 0.2
2
to 2.5 mm
). When connecting two cables to one terminal, use the same cables of
AWG24 to AWG16 (0.2 to 1.5 mm
the cable insulation as shown at right.
• Tighten the mounting screws of the network interface connector to a recommended torque of 0.3 to 0.5 N·m.
• Tighten the terminal screws of the network interface connector to a recommended torque of 0.5 to 0.6 N·m.
• To prevent electrical shocks or communication error due to noises, connect the FG terminal to a proper ground using a
grounding wire of UL1015 AWG22 or UL1007 AWG18 (grounding resistance 100Ω maximum). Do not connect the
grounding wire in common with the grounding wire of motor equipment.
Ferrules, Crimping Tool, and Screwdriver for Phoenix Terminal Blocks
The screw terminal block of the network interface connector can be wired with or without using ferrules on the end of the
cable. Applicable ferrules for the terminal block and crimping tool for the ferrules are listed below. Use a screwdriver to
tighten the screw terminals on the L
available from Phoenix Contact.
Type numbers of Phoenix Contact ferrules, crimping tool, and screwdriver are listed below. When ordering these products
from Phoenix Contact, specify the Order No. and quantity listed below.
• Ferrule Order No.
Applicable Wire Size
2
mm
AWG
0.25
24
0.5
20
0.75
18
1.0
18
1.5
16
2.5
14
For 1-wire Connection
A
8.0 mm
• Crimping Tool and Screwdriver Order No.
Tool Name
Crimping Tool
Screwdriver
6
M
ODULE
Interface Module
W
ON
ORKS
interface module before you start wiring. Make sure wiring is correct before powering up
ORKS
2
). Do not use cables of different diameters. Strip
W
interface module. Ferrules, crimping tool, and screwdriver are made by and
ON
ORKS
For 1-wire connection
Phoenix Type
Order No.
AI 0,25-8 YE
32 00 85 2
AI 0,5-8 WH
32 00 01 4
AI 0,75-8 GY
32 00 51 9
AI 1-8 RD
32 00 03 0
AI 1,5-8 BK
32 00 04 3
AI 2,5-8 BU
32 00 52 2
Dimension
Ferrule
A
4.5 mm
AI 0,25-8 YE
AI 0,5-8 WH
AI 0,75-8 GY
6.0 mm
AI 1-8 RD
AI 1,5-8 BK
AI 2,5-8 BU
CRIMPFOX UD 6
SZS 0,6 x 2,5
O
N
C
L
PEN
ET
ONTROLLER
interface module to the network. Do not run the network cable in
For 2-wire connection
Phoenix Type
AI-TWIN 2 x 0,5-8 WH
AI-TWIN 2 x 0,75-8 GY
AI-TWIN 2 x 1-8 RD
AI-TWIN 2 x 1,5-8 BK
For 2-wire connection
B
Phoenix Type
Order No.
12 04 43 6
12 05 04 0
W
I
M
ON
ORKS
NTERFACE
ODULE
7 mm
Order No.
32 00 93 3
32 00 80 7
32 00 81 0
32 00 82 3
Ferrule
AI-TWIN 2 x 0,5-8 WH
AI-TWIN 2 x 0,75-8 GY
AI-TWIN 2 x 1-8 RD
AI-TWIN 2 x 1,5-8 BK
8.0 mm
Pcs./Pkt.
1
10
U
'
M
SER
S
ANUAL
Pcs./Pkt.
100
100
100
100
100
100
Dimension
B
7.0 mm
8.0 mm

Advertisement

Table of Contents
loading

Table of Contents