Test and Certify an M12 Patch Cord
Patch cord tests include results for the M12 connectors on the ends of
cord. Use this procedure to do tests on M12 cords you make to connect the
components in your system.
1
On the home screen, tap the test setup panel.
2
On the CHANGE TEST screen, tap NEW TEST.
3
On the TEST SETUP screen, tap the panels to select settings:
Cable Type: If the correct type is not in the LAST USED list, tap
MORE, tap Manufacturers, tap the correct manufacturer, then tap
a cable type.
Shield Test: Shows only for shielded cable types. To get a FAIL
result if the shield is open, select On. See the Versiv Series Users
Manual for more information.
Test Limit: If the correct patch cord limit is not in the LAST USED
list, tap MORE, tap Patch Cords, then select the correct limit.
Outlet Configuration: Select the appropriate configuration.
4
On the TEST SETUP screen, tap SAVE when your test setup is
completed.
5
Connect the testers to the patch cord (Figure 5), then tap TEST on the
main tester or press
Main tester with
M12 adapter
8
B
Patch cord under test
To help ensure accurate test
results, do not bend the patch
cord during the test.
Figure 5. Connections for Tests on a Patch Cord
on the main or remote tester.
W
Caution
Remote tester with
M12 adapter
U01.EPS