5.6 and 8.0 k-factor extended coverage horizontal sidewall sprinklers quick and standard response (light hazard)
Hide thumbs Also See for tyco TY-FRB Series:

Advertisement

TFP296
Page 4 of 8
5.6K EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLER (TY3332)
Coverage
Response
Area
(1)
Rating
ft x ft (m x m)
Quick
16 x 16 (4,9 x 4,9)
Quick
16 x 18 (4,9 x 5,5)
Quick
16 x 20 (4.9 x 6,1)
Quick
16 x 22 (4,9 x 6,7)
Standard
16 x 20 (4,9 x 6,1)
Standard
16 x 22 (4,9 x 6,7)
8.0K EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLER (TY4332)
Coverage
Response
Area
(1)
Rating
ft x ft (m x m)
Quick
16 x 16 (4,9 x 4,9)
Quick
16 x 18 (4,9 x 5,5)
Quick
16 x 20 (4.9 x 6,1)
Quick
16 x 20 (4.9 x 6,1)
Quick
16 x 22 (4,9 x 6,7)
Quick
16 x 22 (4,9 x 6,7)
Quick
16 x 24 (4,9 x 7,3)
Quick
16 x 24 (4,9 x 7,3)
Standard
16 x 20 (4.9 x 6,1)
Standard
16 x 20 (4.9 x 6,1)
Standard
16 x 22 (4,9 x 6,7)
Standard
16 x 22 (4,9 x 6,7)
Standard
16 x 24 (4,9 x 7,3)
Standard
16 x 24 (4,9 x 7,3)
Notes:
1. Backwall (where sprinkler is located) by sidewall (length of throw)
2. Requirement is based on minimum flow in gpm from each sprinkler. The indicted residual pressures are based on the nominal K-factor.
3. The centerline of the sprinkler waterway is located 7/16 in. (11,1 mm) below the deflector (Ref. Figures 1 and 2).
4. Minimum spacing is for lateral distance between sprinklers located along a single wall, otherwise adjacent sprinklers (i.e., sidewall sprinklers on an adjacent wall, on an oppo-
site wall, or pendent sprinklers) must be located outside of the maximum listed protection area of the extended coverage sidewall sprinkler being utilized.
5. Minimum spacing is 13 ft (4,0 m) when design pressure exceeds 175 psi (12,1 bar), otherwise the minimum spacing is 10 ft (3 m).
Minimum
Minimum
,
Flow
(2)
,
Pressure
gpm (lpm)
psi (bar)
26 (98)
21.6 (1,48)
29 (110)
26.8 (1,85)
32 (121)
32.7 (2,25)
35 (133)
39.1 (2,70)
32 (121)
32.7 (2,25)
35 (133)
39.1 (2,70)
Minimum
Minimum
,
Flow
(2)
,
Pressure
gpm (lpm)
psi (bar)
26 (98)
10.6 (0,73)
29 (110)
13.1 (0,90)
32 (121)
16.0 (1,10)
33 (125)
17.0 (1,17)
35 (133)
19.1 (1,32)
36 (136)
20.3 (1,59)
39 (148)
23.8 (1,64)
40 (151)
25.0 (1,72)
32 (121)
16.0 (1,10)
33 (125)
17.0 (1,17)
35 (133)
19.1 (1,32)
36 (136)
20.3 (1,59)
39 (148)
23.8 (1,64)
40 (151)
25.0 (1,72)
UL AND C-UL LISTING COVERAGE AND FLOW RATE CRITERIA
Deflector-to-Ceiling
(2)
,
Distance
(3)
,
Inches (mm)
4 to 12 (100 to 300)
4 to 12 (100 to 300)
4 to 6 (100 to 150)
4 to 6 (100 to 150)
4 to 6 (100 to 150)
4 to 6 (100 to 150)
Deflector-to-Ceiling
(2)
,
Distance
(3)
,
Inches (mm)
4 to 12 (100 to 300)
4 to 12 (100 to 300)
4 to 6 (100 to 150)
4 to 12 (100 to 300)
4 to 6 (100 to 150)
4 to 12 (100 to 300)
4 to 6 (100 to 150)
4 to 12 (100 to 300)
4 to 6 (100 to 150)
4 to 12 (100 to 300)
4 to 6 (100 to 150)
4 to 12 (100 to 300)
4 to 6 (100 to 150)
4 to 12 (100 to 300)
TABLE C
Sprinkler
Minimum
Temperature
Spacing
Rating, °F
ft (m)
135, 155, 175
10 (3,1)
135, 155, 175
10 (3,1)
135
10 (3,1)
135
10 (3,1)
155
10 (3,1)
155, 175
10 (3,1)
Sprinkler
Minimum
Temperature
Spacing
Rating, °F
ft (m)
135, 155, 175
10 (3,1)/13 (4,0)
135, 155, 175
10 (3,1)/13 (4,0)
135
10 (3,1)/13 (4,0)
135
10 (3,1)/13 (4,0)
135
10 (3,1)/13 (4,0)
135
10 (3,1)/13 (4,0)
135
10 (3,1)/13 (4,0)
135
10 (3,1)/13 (4,0)
155
10 (3,1)/13 (4,0)
155
10 (3,1)/13 (4,0)
155, 175
10 (3,1)/13 (4,0)
155, 175
10 (3,1)/13 (4,0)
155, 175
10 (3,1)/13 (4,0)
155, 175
10 (3,1)/13 (4,0)
(4)
,
(4)
,
(5)
(5)
(5)
(5)
(5)
(5)
(5)
(5)
(5)
(5)
(5)
(5)
(5)
(5)