Series TY-FRL – 5.6 K-factor
Horizontal Sidewall Sprinkler
Quick Response, Standard Coverage
General
Description
TYCO Series TY-FRL 5.6K Horizon-
tal Sidewall Sprinklers (HSW), Quick
Response, Standard Coverage are sol-
der-type spray sprinklers designed for
use in light and ordinary hazard com-
mercial occupancies such as banks,
hotels, shopping malls, offices, etc.
They are designed for installation along
a wall or the side of a beam and just
beneath a smooth ceiling. Horizontal
sidewall sprinklers are commonly used
instead of pendent or upright sprin-
klers due to aesthetics or building con-
struction considerations, where piping
across the ceiling is not desirable.
NOTICE
The
Series
T Y-FRL
described herein must be installed
and maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association (NFPA), in addition
to the standards of any other authori-
ties having jurisdiction. Failure to do so
may impair the performance of these
devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 4
Sprinkler
Identification
Numbers (SINs)
TY3321 – HSW 5.6K, 1/2 in. NPT
TY3321 is a re-designation for Star SIN
S1878 and Gem SIN G8946.
Technical
Data
Approvals
UL and C-UL Listed
FM and NYC Approved
(Refer to Table A for complete approval
information.)
Maximum Working Pressure
175 psi (12,1 bar)
Sprinklers
Discharge Coefficient
K=5.6 gpm/psi
Temperature Ratings
Refer to Table A
Finishes
Refer to Table A
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Strut. . . . . . . . . . . . . . . . . . . . . . . . . . . . . MONEL
Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Hook . . . . . . . . . . . . . . . . . . . . . . . . . . . . MONEL
Link Assembly . . . . . . . . . . . . . . . . . . . . . . Nickel
Ejection Spring . . . . . . . . . . . . . . . . . . INCONEL
Button . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Seal . . . . . . . . . . . . . . . . . . . . . . . . . . . . .TEFLON
AUGUST 2018
½
(80,6 lpm/bar
½
)
Worldwide
www.tyco-fire.com
Contacts
Operation
The fusible link (heat collector) assem-
bly is comprised of two halves that
are joined together by a thin layer of
solder. When the rated temperature is
reached, the solder melts and the two
link halves separate, allowing the sprin-
kler to operate.
Design
Criteria
TYCO Series TY-FRL 5.6K HSW Sprin-
klers, Quick Response, Standard
Coverage are intended for fire pro-
tection systems designed in accor-
dance with the standard installation
rules recognized by the applicable
listing or approval agency (e.g., UL
Listing is based on NFPA 13 require-
ments); however, the minimum dis-
tance between sprinklers to prevent
cold soldering is 8 ft (2,4 m). The
Series T Y-FRL HSW Sprinklers
must be installed with a deflector-
to-ceiling distance of 4 in. to 6 in.
(100 mm to 150 mm). To meet this
requirement the centerline of the
sprinkler waterway must be located
4-5/16 in. to 6-5/16 in. (110 mm to
160 mm) below the ceiling. Installation
of the Series TY-FRL HSW Sprinklers
in recessed escutcheons will void all
manufacturer's warranties, as well as
possibly void the sprinkler's approvals
and/or listings.
TFP140

Advertisement

loading
Need help?

Need help?

Do you have a question about the tyco TY-FRL Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Johnson Controls tyco TY-FRL Series

  • Page 1 Worldwide www.tyco-fire.com Contacts Series TY-FRL – 5.6 K-factor Horizontal Sidewall Sprinkler Quick Response, Standard Coverage General Sprinkler Description Identification Numbers (SINs) TYCO Series TY-FRL 5.6K Horizon- tal Sidewall Sprinklers (HSW), Quick Response, Standard Coverage are sol- TY3321 – HSW 5.6K, 1/2 in. NPT der-type spray sprinklers designed for TY3321 is a re-designation for Star SIN use in light and ordinary hazard com-...
  • Page 2 TFP140 Page 2 of 4 SPRINKLER FINISH SPRINKLER TEMPERATURE FRAME FACTOR TYPE RATING COLOR CODE NATURAL CHROME BRASS PLATED 165°F (74°C) Unpainted HORIZONTAL SIDEWALL 1, 2, 3, 4 1/2 in. NPT (TY3321) White 212°F (100°C) Notes: 1. UL Listed for light or ordinary hazard occupancies as Quick Response sprinklers 2.
  • Page 3 TFP140 Page 3 of 4 P/N 58 — XXX — X — XXX SPRINKLER TEMPERATURE FINISH RATING NATURAL 5.6K HSW (1/2 in. NPT) TY3321 165°F (74°C) BRASS CHROME 212°F (100°C) PLATED TABLE B SERIES TY-FRL HORIZONTAL SIDEWALL SPRINKLERS, QUICK RESPONSE PART NUMBER SELECTION Care and Limited...
  • Page 4 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700 © 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice. NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;...