Series TY-B & TY-FRB, 10 mm Orifice, ISO 7-R 3/8
Upright, Pendent, and Recessed Pendent Sprinklers
Standard and Quick Response
General
Description
The TYCO Series TY-B (5 mm Bulb)
and TY-FRB (3 mm Bulb), 10 mm
orifice Upright and Pendent Sprinklers
are automatic sprinklers of the fran-
gible bulb type. They are spray sprin-
klers intended for use in fire sprinkler
systems designed in accordance with
the installation rules recognized by
the applicable approval agency. Both
the Upright and Pendent Sprinklers
produce a hemispherical water distri-
bution pattern below the deflector.
The recessed version of the Series
TY-B and TY-FRB Pendent Sprinklers,
where applicable, are intended for use
in areas with a finished ceiling. They
use a two-piece Style 70 (3/8 inch NPT)
Recessed Escutcheon with 12 mm of
recessed adjustment or up to 20 mm of
total adjustment from the flush pendent
position. The adjustment provided by
the Recessed Escutcheon reduces the
accuracy to which the fixed pipe drops
to the sprinklers must be cut.
NOTICE
The Series TY-B and TY-FRB Sprinklers
described herein must be installed
and maintained in compliance with
this document and with the applicable
standards recognized by the Approval
Agency, in addition to the standards of
any other authorities having jurisdiction.
Failure to do so may impair the perfor-
mance of these devices.
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 4
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
Sprinkler
Identification
Number (SIN)
TY2108 . . . . . . . . . . . . . . . . Upright, 5 mm bulb
TY2208 . . . . . . . . . . . . . . . Pendent, 5 mm bulb
TY2109 . . . . . . . . . . . . . . . . Upright, 3 mm bulb
TY2209 . . . . . . . . . . . . . . . Pendent, 3 mm bulb
Technical
Data
Approvals
LPCB and VdS Approved
Refer to Table A
Maximum Working Pressure
12,1 bar
Discharge Coefficient
K = 58 lpm/bar
1/2
Temperature Rating
Refer to Table A
Finishes
Refer to Table A
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Button . . . . . . . . . . . . . . . . . . . . . . Brass/Copper
Sealing Assembly . . . . Beryllium Nickel w/Teflon
Bulb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Glass
Compression Screw . . . . . . . . . . . . . . . . .Bronze
Deflector . . . . . . . . . . . . . . . . . . . . . . . . . Copper
Operation
The glass Bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass Bulb, allowing the sprinkler to
activate and water to flow.
AUGUST 2018
Worldwide
www.tyco-fire.com
Contacts
Design
Criteria
The TYCO Series TY-B and TY-FRB
10 mm Orifice Pendent and Upright
Sprinklers are intended for fire protec-
tion systems designed in accordance
with the standard installation rules
recognized by the applicable approval
agency. Only the Style 70 Escutcheon
is to be used for recessed pendent
installation.
TFP670

Advertisement

loading
Need help?

Need help?

Do you have a question about the tyco TY-B Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Johnson Controls tyco TY-B Series

  • Page 1 Worldwide www.tyco-fire.com Contacts Series TY-B & TY-FRB, 10 mm Orifice, ISO 7-R 3/8 Upright, Pendent, and Recessed Pendent Sprinklers Standard and Quick Response General The owner is responsible for main- taining their fire protection system Description and devices in proper operating con- dition.
  • Page 2 2. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response. 3. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Unclassified Response. 4. VdS Approved For details, contact Johnson Controls, Enschede, The Netherlands, Tel. 31-53-428-4444/Fax 31-53-428-3377. ***Frame and deflector only. N/A: Not Available...
  • Page 3 TFP670 Page 3 of 4 Frame Bulb: Compression Temperature rating is indicated on Deflector Button 5 mm Dia. for TY-B Screw or adjacent to orifice seat on Frame 6 - Deflector Sealing Assembly 3 mm Dia. for TY-FRB ESCUTCHEON PLATE STYLE 70 SEATING SURFACE RECESSED ESCUTCHEON...
  • Page 4 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700 © 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice. NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;...

This manual is also suitable for:

Tyco ty-frb seriesTyco ty2108Tyco ty2208Tyco ty2109Tyco ty2209