Refrigerant Piping Insulation; Refrigerant Piping Length And Height Difference; Connecting The Refrigerant Piping - Daikin R32 Split Series Installer's Reference Manual

Hide thumbs Also See for R32 Split Series:
Table of Contents

Advertisement

7
|
Piping installation

7.1.2 Refrigerant piping insulation

7.1.3 Refrigerant piping length and height difference

7.2 Connecting the refrigerant piping

Installer reference guide
36
Use polyethylene foam as insulation material:
-
with a heat transfer rate between 0.041 and 0.052  W/mK (0.035 and
0.045 kcal/mh°C)
-
with a heat resistance of at least 120°C
Insulation thickness
Pipe outer diameter (Ø
6.4 mm (1/4")
9.5 mm (3/8")
12.7 mm (1/2")
15.9 mm (5/8")
Ø
Ø
i
i
Ø
Ø
p
p
t
If the temperature is higher than 30°C and the humidity is higher than RH 80%, the
thickness of the insulation materials should be at least 20  mm to prevent
condensation on the surface of the insulation.
What?
Maximum allowable pipe length
Minimum allowable pipe length
Maximum allowable height distance
CAUTION
No brazing or welding on site for units with R32 refrigerant charge during
shipment.
During installation of the refrigeration system, joining of parts with at least one
part charged shall be performed taking into account the following requirements:
ð inside occupied spaces non permanent joints are not allowed for R32 refrigerant
except for site made joints directly connecting the indoor unit to piping. Site
made joints directly connecting piping to indoor units shall be of non permanent
type.
WARNING
Only use R32 as refrigerant. Other substances may cause explosions and
accidents.
R32 contains fluorinated greenhouse gases. Its global warming potential (GWP)
value is 675. Do NOT vent these gases into the atmosphere.
When charging refrigerant, ALWAYS use protective gloves and safety glasses.
) Insulation inner diameter
p
)
i
8~10 mm
10~14 mm
14~16 mm
16~20 mm
ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B +
RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B
Insulation thickness (t)
≥10 mm
≥13 mm
≥10 mm
≥13 mm
Distance
30 m
3 m
20 m
R32 split series
4P513661-9J – 2020.05