3. Current release control
The output frequency and the output voltage are controlled by AC current value detected by current transformer
on the outdoor P.C. board so that input current of the inverter does not exceed the specified value.
Current [A]
I1
Hold
I1 – 0.5
Normal operation
4. Outdoor fan control
W1
W2
UPPER
250
280
LOWER
250
280
4-1. Cooling fan control
1) An outdoor fan is controlled by TL sensor, TO sensor and compressor frequency. An outdoor fan is
controlled at 1-tap interval of DC fan control.
2) At the start time, the fan is fixed for 60 seconds only with the maximum fan tap corresponded to the zone
in the following table but it is controlled with TL sensor temperature after then.
GM1601 : WF tap
TL
58˚C
55˚C
+
1 tap / 20 sec (Up to the maximum
rotational frequency of each zone)
37˚C
Rotational frequency hold
34˚C
– 1 tap / 20 sec
(Up to the minimum rotational
frequency of each zone)
Frequency down
Hold
Allocations of fan tap revolutions [rpm]
W3
W4
W5
W6
330
360
410
460
330
340
410
440
Temp.
range
38°C ≤ TO
29°C ≤ TO < 38°C
15°C ≤ TO < 29°C
5°C ≤ TO < 15°C
0°C ≤ TO < 5°C
–4°C ≤ TO < 0°C
TO < –4°C
Model
I1 value [A]
W7
W8
W9
520
580
650
500
560
600
20.4Hz or lower 20.4Hz to 45.0Hz 45.0Hz or higher
Min.
Max.
W6
W5
W4
W3
W2
W2
OFF
TO error
OFF
- 45 -
GM160
COOL
HEAT
29
29
WA
WB
WC
WD
700
760
830
860
660
700
780
820
Min.
Max.
WC
W8
WF
WB
W7
WE
W8
W6
WA
W6
W5
W8
W4
W4
W6
W3
W3
W5
W1
OFF
W1
WC
OFF
WF
WE
WF
940
980
940
980
Min.
Max.
WA
WF
W9
WE
W8
WC
W7
WA
W5
W8
W4
W6
W2
W7
W2
WF