AIR CONDITIONER (SPLIT TYPE) Outdoor Unit For commercial use Installation Manual Model name: <Heat Pump Model> RAV-GM1601AT8P-E RAV-GM1601AT8JP-E Scan QR CODE to access installation and owner’s manual on website. https://www.toshiba-carrier.co.th/manuals/default.aspx Manual are available in AR/BG/CZ/DA/DE/EL/EN/ES/ET/FI/FR/ HR/HU/IT/LT/LV/NL/NO/PL/PT/RO/RU/SK/SL/SV/TR. English...
– 1 – Contents Original instruction Please read this Installation Manual carefully before installing the Air Conditioner. This Manual describes the installation method of the outdoor unit. Accessory parts ........... . . 3 For installation of the indoor unit, follow the Installation Manual attached to the indoor unit.
Page 3
Cautions for outdoor unit installation space Center of gravity In the event that the outdoor unit is installed in a small space and refrigerant leaks, accumulation of highly concentrated (Unit: mm) Center of gravity the installation space instructions in the Installation Manual, and provide open space on at least one of the four outdoor unit sides.
– 3 – Accessory parts Installation of R32 refrigerant air conditioner Part name Q’ty Shape Usage Installation Manual Booklet For hand this directly to the customer. CAUTION R32 refrigerant air conditioner installation Drain nipple This air conditioner adopts the HFC refrigerant (R32) which does not destroy ozone layer. Therefore, during installation work, make sure that water, dust, former refrigerant, or refrigerant oil does not enter the R32 refrigerant air conditioner cycle.
Installation conditions Bender Bending pipes Conventional tools (R410A) Refrigerant recovery equipment Refrigerant recovery Conventional tools (R32 or R410A) Before installation Electrical wiring Torque wrench Conventional tools (R410A) Be sure to prepare to the following items before interconnection wires with clamps so that they do not installation.
Page 6
– 5 – Installation location Necessary space for installation (Unit: mm) CAUTION Single unit installation WARNING Install the outdoor unit in a location where Install the outdoor unit properly in a location that When an outdoor unit is installed in a is durable enough to support the weight of the When there is an obstacle on the When there is an obstacle on the...
Page 7
Installation of outdoor unit Serial unit installation Set the out margin of the anchor bolt to 15 mm or less. * When the outdoor temperature is high, the cooling capability may be decreased because of an equipment Before installation, check the strength and protection operation.
– 7 – Refrigerant piping connection Refrigerant piping Flaring dia. size: A (Unit: mm) CAUTION Refrigerant Piping IMPORTANT 4 POINTS FOR PIPING WORK 1. Use the following items for the refrigerant piping. joints are not allowed indoors. When mechanical Material : Seamless phosphorous deoxidized connectors are reused indoors, sealing parts shall Outer dia.
Page 9
Refrigerant pipe length (Unit: N•m) Tightening torque Single 9.5 mm (dia.) 34 to 42 (3.4 to 4.2 kgf•m) 15.9 mm (dia.) 68 to 82 (6.8 to 8.2 kgf•m) Allowable pipe length (m) Height difference (Indoor-outdoor H) (m) Total length L Indoor unit: Upper Outdoor unit: Lower Cover...
– 9 – Air purge Air purging Vacuum pump With respect to the preservation of the terrestrial Airtight test environment, adopt “Vacuum pump” to purge air the manifold valve is closed completely. (Evacuate air in the connecting pipes) when installing After completing the refrigerant piping work, perform an airtight test.
Page 11
Replenishing refrigerant Charging additional refrigerant Fully open the valves of the outdoor unit. (First fully This model is a 30 m chargeless type that does not Figure of Single Figure of simultaneous twin Figure of Simultaneous triple open the valve on the liquid side, and then fully open need to have its refrigerant replenished for refrigerant Indoor unit Indoor unit...
– 11 – Gas leak inspection Electrical work Indoor unit inspection locations Use a leak detector manufactured specially for HFC refrigerant (piping connections) (R32, R410A, R134a, etc.) to perform the R32 gas leak inspection. Remove the service panel, and you can see electric Refrigerant WARNING parts on the front side.
Page 13
For the air conditioner, connect a power wire with the Stripping length power cord and Simultaneous triple system connecting wire Remote controller Remote controller Remote controller Remote controller Model RAV- GM160 inter-unit wiring inter-unit wiring wiring 380-415 V 3N ~, 50 Hz Power supply 380 V 3N ~, 60 Hz Indoor side...
– 13 – Earthing Functions to be implemented locally WARNING Handling existing pipe Be sure to connect the earth wire. (grounding work) When using the existing pipe, carefully check for the following: Incomplete grounding may cause an electric shock. Scratches and dents Connect the earth wire properly following applicable technical standards.
Refrigerant recovery Troubleshooting You can perform fault diagnosis of the outdoor unit with the LEDs on the P.C. board of the outdoor unit in addition WARNING to using the check codes displayed on the wired remote controller of the indoor unit. Use the LEDs and check codes for various checks.
– 15 – Appendix Branching pipe for simultaneous operation system In the concurrent twin system, when TOSHIBA has [1] Existing piping 4. When refrigerant cannot be recovered using a refrigerant recovery unit. reused. There is the possibility that a large quantity of dirty...
Page 17
[2] Minimum area : A (m²) Existing pipes: Cannot be used. Are there scratches or dents on the existing pipes? Use new pipes. Total Ceiling Floor standing Wall mounted refrigerant mounted Is it possible to operate the existing air conditioner? unit unit quantity*...
– 17 – (m²) Sound power level (dBA) Model Weight (kg) Cooling Heating RAV-GM1601AT8P-E RAV-GM1601AT8JP-E Product information of ecodesign requirements, (Regulation (EU) 2016/2281) http://ecodesign.toshiba-airconditioning.eu/en M (kg) 33-EN 34-EN...
Page 19
To Fix the Fluorinated Fill in the label as follows: Greenhouse Gases Label Manufacturer: Toshiba Carrier (Thailand) Co., Ltd. 144 / 9 Moo 5, Bangkadi Industrial Park, Tivanon Road, Tambol Bangkadi, Do not vent gases into the atmosphere. Amphur Muang, Pathumthani 12000, Thailand...
Page 20
– 19 – Warnings on refrigerant leakage Check of concentration limit The refrigerant R32 which is used in the air conditioner is safe, without the toxicity or combustibility of ammonia, and is not restricted by laws to be imposed which protect the ozone layer. However, since it contains more than air, it poses the risk of suffocation if its concentration should rise excessively.