Fujitsu AS G07KGTA Series Service Instruction page 45

Split type room air conditioner, wall mounted type inverter
Table of Contents

Advertisement

Trouble shooting 16
OUTDOOR UNIT Error Method:
Outdoor unit main PCB error
Detective Actuators:
Outdoor unit Main PCB
Forecast of Cause:
1. External cause (Noise, temporary open, voltage drop)
Check Point 1-1 : Reset Power Supply and operate
Does Error indication show again?
YES
YES
Check Point 2 : Replace Main PCB
Change Main PCB.
Indicate or Display:
Outdoor Unit : No indication
Indoor Unit
: Operation lamp: 6 time Flash, Timer lamp: 2 time Flash
Economy lamp: Continuous flash.
ERROR CODE : [E : 62 ]
Detective details:
Access to EEPROM failed due to some cause after outdoor unit started.
NO
Check Point 1-2 : Check external cause
Check if temporary voltage drop was not generated.
Check if momentary open was not generated.
Check if ground is connection correctly or there are no
related cables near the power line.
02-19
2. Main PCB failure