AIR CONDITIONER

Wall Mounted type

DESIGN & TECHNICAL MANUAL
INDOOR
OUTDOOR
AS  G07LMCA
AS  G09LMCA
AS  G12LMCA
AS  G14LMCA
AO  G07LMCA
AO  G09LMCA
AO  G12LMCA
AO  G14LMCA

Advertisement

Table of Contents
loading

Summary of Contents for Fujitsu G09LMCA

  • Page 1: Air Conditioner

    AIR CONDITIONER Wall Mounted type DESIGN & TECHNICAL MANUAL INDOOR AS  G07LMCA AS  G09LMCA AS  G12LMCA AS  G14LMCA OUTDOOR AO  G07LMCA AO  G14LMCA AO  G09LMCA AO  G12LMCA...
  • Page 2 1. INDOOR UNIT WALL MOUNTED TYPE : ASG07LMCA ASG09LMCA ASG12LMCA ASG14LMCA DTR_AS076E_05 2015.01.16...
  • Page 3: Table Of Contents

    CONTENTS 1. INDOOR UNIT 1. FEATURES ......................01 - 01 2. WIRELESS REMOTE CONTROLLER ..........01 - 03 3. SPECIFICATIONS ....................01 - 05 4. DIMENSIONS ......................01 - 07 5. WIRING DIAGRAMS ..................01 - 09 6. CAPACITY TABLE ....................
  • Page 4: Indoor Unit

    FEATURES „ „ MODELS ASG07LMCA / AOG07LMCA ASG09LMCA / AOG09LMCA ASG12LMCA / AOG12LMCA ASG14LMCA / AOG14LMCA AO  G07LMCA AO  G14LMCA AO  G09LMCA AO  G12LMCA „ „ FEATURES Energy efficiency class „ MODEL AS  G07LMCA AS  G09LMCA AS ...
  • Page 5: Powerful Operation

    10°C HEAT Operation „ The room temperature can be set to go no lower than 10°C, thus ensuring that the room does not get too cold when not occupied. NOTE: • When the room temperature is higher than 10°C, “10°C HEAT” operation will not start. Operation starts and maintains the room temperature at 10°C when the temperature drops below 10°C.
  • Page 6: Wireless Remote Controller

    WIRELESS REMOTE CONTROLLER „ „ FEATURES 4 mode timer setup available (ON / OFF / PROGRAM / SLEEP).  „ Easy operation.  „ Easy to change custom code (max. 4 custom codes) by button  „ operation. Simple function setting „...
  • Page 7 „ „ FUNCTIONS Signal Transmitter 10 °C HEAT button MODE button ECONOMY button OUTDOOR UNIT LOW NOISE button ON TIMER button OFF TIMER button CLOCK ADJUST button POWERFUL button TEMP. Set button ( Start/Stop button FAN button SWING button SET button SLEEP TIMER button CANCEL button RESET button...
  • Page 8: Specifications

    SPECIFICATIONS WALL MOUNTED Type INVERTER HEAT PUMP Model name ASG07LMCA ASG09LMCA ASG12LMCA ASG14LMCA Power source 230V~ 50Hz Available voltage range 198-264V~ 50Hz 2.00 2.50 3.40 4.00 Rated Btu/h 6,800 8,500 11,600 13,600 Cooling 0.5~3.0 0.5 - 3.2 0.9 - 3.9 0.9~4.4...
  • Page 9 Model name ASG07LMCA ASG09LMCA ASG12LMCA ASG14LMCA Cooling Energy efficiency class Heating (Average) 2.0 (35°C) 2.5 (35°C) 3.4 (35°C) 4.0 (35°C) Cooling Pdesign 2.3 (-10°C) 2.4 (-10°C) 3.5 (-10°C) 3.9 (-10°C) Heating (Average) SEER Cooling 6.80 7.00 7.00 6.90 kWh/kWh SCOP Heating (Average) 4.10...
  • Page 10: Dimensions

    DIMENSIONS „ „ MODELS :ASG07LMCA, ASG09LMCA, ASG12LMCA, ASG14LMCA (Unit : mm) - (01 - 07) -...
  • Page 11 „ „ INSTALLATION PLACE (Unit : mm) - (01 - 08) -...
  • Page 12: Wiring Diagrams

    WIRING DIAGRAMS „ „ MODELS :ASG07LMCA, ASG09LMCA, ASG12LMCA, ASG14LMCA - (01 - 09) -...
  • Page 13: Capacity Table

    0.45 1.50 1.01 0.46 1.60 1.01 0.46 1.65 1.09 0.46 1.75 1.09 0.47 1.85 1.16 0.47 „ „ MODEL : ASG09LMCA 12.5 Indoor temperature °CDB °CWB °CDB 2.34 1.62 0.46 2.61 1.63 0.46 2.70 1.77 0.47 2.87 1.78 0.47 2.96 1.92...
  • Page 14: Heating Capacity

    3.79 1.24 3.69 1.26 3.60 1.29 3.72 1.09 3.63 1.12 3.54 1.14 3.45 1.16 3.36 1.18 „ „ MODEL : ASG09LMCA 12.5 Indoor temperature (°CDB) (°CDB) (°CWB) 1.72 0.71 1.68 0.73 1.64 0.74 1.60 0.75 1.56 0.77 2.38 0.86 2.33 0.88...
  • Page 15: Fan Performance

    Conditions: Fan speed: HIGH Operation mode: FAN 7-1. AIR VELOCITY DISTRIBUTION „ „ MODELS :ASG07LMCA, ASG09LMCA, ASG12LMCA Unit : m/s TOP VIEW Vertical flap: Up Horizontal flap: Center Unit : m/s TOP VIEW Vertical flap: Up Horizontal flap: Right & Left...
  • Page 16 Conditions: Fan speed: HIGH „ „ MODEL : ASG14LMCA Operation mode: FAN Unit : m/s TOP VIEW Vertical flap: Up Horizontal flap: Center Unit : m/s TOP VIEW Vertical flap: Up Horizontal flap: Right & Left Unit : m/s SIDE VIEW Vertical flap: Up Horizontal flap: Center Unit : m/s...
  • Page 17: Air Flow

    7-2. AIR FLOW „ „ MODELS :ASG07LMCA, ASG09LMCA, ASG12LMCA Cooling „ Number of Fan speed rotations Air flow (r.p.m.) HIGH 1320 1160 QUIET Heating „ Number of Fan speed rotations Air flow (r.p.m.) HIGH 1320 1160 QUIET - (01 - 14) -...
  • Page 18 „ „ MODEL : ASG14LMCA Cooling „ Number of Fan speed rotations Air flow (r.p.m.) HIGH 1360 1220 QUIET Heating „ Number of Fan speed rotations Air flow (r.p.m.) HIGH 1360 1220 1040 QUIET - (01 - 15) -...
  • Page 19: Operation Noise (Sound Pressure)

    2,000 2,000 4,000 4,000 8,000 8,000 Octave band center frequency,Hz Octave band center frequency,Hz Octave band center frequency,Hz Octave band center frequency,Hz „ „ MODEL : ASG09LMCA Cooling Heating „ „ NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH...
  • Page 20 „ „ MODEL : ASG12LMCA Cooling Heating „ „ NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH HIGH NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 QUIET QUIET 1,000 1,000 2,000 2,000 4,000 4,000 8,000 8,000...
  • Page 21: Sound Level Check Point

    8-2. SOUND LEVEL CHECK POINT - (01 - 18) -...
  • Page 22: Electrical Characteristics

    ELECTRICAL CHARACTERISTICS Model name ASG07LMCA ASG09LMCA ASG12LMCA ASG14LMCA Voltage 230~ Power supply Frequency Max. operating current Connection cable Wiring spec. *1 Limited wiring length *1: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005. - (01 - 19) -...
  • Page 23: Safety Devices

    SAFETY DEVICES Model ASG07LMCA Protection form ASG09LMCA ASG12LMCA ASG14LMCA Circuit protection Current fuse (PC board) 250V 3.15A OFF: 105 ± 10 °C Fan motor protection Thermal protector program ON: 90 ± 10 °C - (01 - 20) -...
  • Page 24: External Input & Output

    EXTERNAL INPUT & OUTPUT Connector INPUT OUTPUT REMARKS Control input See external CNA01 CNB01 Operation status output input/output settings for details. CNB02 Error status output 11-1. EXTERNAL INPUT CONTROL INPUT (Operation/Stop or Forced stop) „ „ The air conditioner can be remotely operated by means of the following on-site work. "Operation/Stop"...
  • Page 25 When function setting is in "Forced stop" mode „ Input signal Forced stop Command Normal Operation Indoor unit Stop Remote controller Remote control operation invalidity Parts (Optional) „ Parts name Model name External connect kit UTY-XWZXZ5 Communication kit UTY-XCBXZ2 * For operating the EXTERNAL function, the wall mounted type requires the communication kit in addition to the wire (UTY-XWZXZ5).
  • Page 26: External Output

    11-2. EXTERNAL OUTPUT „ „ OPERATION STATUS OUTPUT An air conditioner operation status signal can be output. Circuit diagram example „ Indoor unit control PC board Communication kit Connected unit Connector 24V DC Ex.)Relay unit Ex.)Display Relay power supply *10 m Signal Optional parts Field supply...
  • Page 27 „ „ ERROR STATUS OUTPUT An air conditioner error status signal can be output. Circuit diagram example „ Indoor unit control PC board Communication kit Connected unit Connector 24V DC Ex.)Relay unit Ex.)Display Relay power supply *10 m Signal Optional parts Field supply *: Make the distance from the PC board to the connected unit within 10 m.
  • Page 28: Function Settings

    FUNCTION SETTINGS INDOOR UNIT (Setting by remote controller) 12-1. • The function settings of the control of the indoor unit can be changed by this procedure according to the installation conditions. Incorrect settings can cause the indoor unit to malfunction. •...
  • Page 29: Function Details

    „ „ FUNCTION DETAILS Functions 1) Filter sign 2) Room temperature control for cooling 3) Room temperature control for heating 4) Auto restart 5) Room temperature sensor switching 6) Remote controller custom code 7) External input control 8) Room temperature sensor switching (Aux.) 9) Indoor unit fan control for energy saving for cooling 1) Filter sign Select appropriate intervals for displaying the filter sign on the indoor unit according to the...
  • Page 30 4) Auto restart Enable or disable automatic restart after a power interruption. (  ... Factory setting) Setting description Function number Setting value Enable  Disable * Auto restart is an emergency function such as for power outage etc. Do not attempt to use this function in normal operation.
  • Page 31 9) Indoor unit fan control for energy saving for cooling Enables or disables the power-saving function by controlling the indoor unit fan rotation when the outdoor unit is stopped during cooling operation. (  ... Factory setting) Setting description Function number Setting value Disable Enable...
  • Page 32 „ „ REMOTE CONTROLLER CUSTOM CODE SETTING Use the following steps to select the custom code of the remote controller. (Note that the air conditioner cannot receive a signal if the right custom code has not been set.) Press the START/STOP button until only the clock is displayed on the remote controller display.
  • Page 33: Optional Parts

    OPTIONAL PARTS 13-1. CONTROLLERS Exterior Parts name Model No. Summary Large and full-dot liquid crystal screen, wide and large keys Wired remote easy to press, user-intuitive UTY-RVNM controller arrow key. *Optional communication kit is necessary for installation. The room temperature can be controlled by detecting the Wired remote temperature accurately with...
  • Page 34: Outdoor Unit

    2.OUTDOOR UNIT SINGLE TYPE : AO G07LMCA AO G09LMCA AO G12LMCA AO G14LMCA DTR_AO130E_05 2015.01.16...
  • Page 35 CONTENTS 2. OUTDOOR UNIT 1. SPECIFICATIONS ....................02 - 01 2. DIMENSIONS ......................02 - 02 3. REFRIGERANT CIRCUIT ................02 - 04 4. WIRING DIAGRAMS ..................02 - 05 5. CAPACITY COMPENSATION RATE FOR PIPE LENGTH AND HEIGHT DIFFERENCE ..............
  • Page 36: Specifications

    SPECIFICATIONS INVERTER COOLING & HEATING Type Model name AOÛG07LMCA AOÛG09LMCA AOÛG12LMCA AOÛG14LMCA Power source 230 V~ 50 Hz Available voltage range 198-264 V Starting current Cooling 1,670 1,830 1,940 Air flow rate Heating 1,470 1,600 1,700 Type × Q'ty Propeller fan × 1...
  • Page 37: Dimensions

    DIMENSIONS „ „ MODELS :AOG07LMCA, AOG09LMCA, AOG12LMCA (Unit : mm) „ „ INSTALLATION PLACE CAUTION When the outdoor temperature is 0 °C or less, do not use the accessory drain pipe and drain cap. If the drain pipe and drain cap...
  • Page 38 „ „ MODEL : AOG14LMCA (Unit : mm) Top view Front view Side view Airflow Drain pipe 4-ø11.3mm hole mounting place (ø20) Bottom view „ „ INSTALLAT ION PLACE CAUTION When the outdoor temperature is 0 °C or less, do not use the accessory drain pipe and drain cap.
  • Page 39: Refrigerant Circuit

    REFRIGERANT CIRCUIT „ „ MODELS :AOG07LMCA, AOG09LMCA, AOG12LMCA, AOG14LMCA : Cooling : Heating Refrigerant pipe diameter Liquid: 1/4" (6.35mm) Gas: 3/8" (9.52 mm): AO*G07LMCA, AO*G09LMCA, AO*G12LMCA 1/2" (12.70 mm): AO*G14LMCA - (02 - 04) -...
  • Page 40: Wiring Diagrams

    WIRING DIAGRAMS „ „ MODELS :AOG07LMCA, AOG09LMCA - (02 - 05) -...
  • Page 41 „ „ MODEL : AOG12LMCA - (02 - 06) -...
  • Page 42 „ „ MODEL : AOG14LMCA - (02 - 07) -...
  • Page 43: Capacity Compensation Rate For Pipe Length And Height Difference

    CAPACITY COMPENSATION RATE FOR PIPE LENGTH AND HEIGHT DIFFERENCE „ „ G07LMCA, AOG09LMCA MODEL: AO Pipe length (m) COOLING 0.910 0.872 Û 1 0.961 0.925 0.886 Indoor unit is higher 0.979 0.965 0.890 0.929 than outdoor unit. 0.992 0.983 0.969 0.893...
  • Page 44 „ „ MODEL : AOG12LMCA Pipe length (m) COOLING 0.858 0.868 Û 1 0.929 0.872 0.882 Indoor unit is higher 0.960 0.933 0.876 0.885 than outdoor unit. 0.992 0.964 0.937 0.879 0.889 Height difference H 0.972 0.944 0.896 1.000 0.887 0.972 0.944 0.896...
  • Page 45 „ „ MODEL : AOG14LMCA Pipe length (m) COOLING 0.893 0.909 Û 1 0.955 0.908 0.924 Indoor unit is higher 0.975 0.959 0.912 0.928 than outdoor unit. 0.992 0.979 0.963 0.916 0.931 Height difference H 0.987 0.970 0.923 0.939 1.000 0.987 0.970 0.923...
  • Page 46: Additional Charge Calculation

    ADDITIONAL CHARGE CALCULATION „ „ MODELS :AOG07LMCA, AOG09LMCA Refrigerant type Refrigerant type R410A R410A Refrigerant amount Refrigerant amount „ Refrigerant charge Total pipe length 15 or less 20 (Max.) 20g/m Additional charge „ „ MODEL : AOG12LMCA Refrigerant type R410A Refrigerant amount „...
  • Page 47: Air Flow

    AIR FLOW „ „ MODELS :AOG07LMCA, AOG09LMCA „ Cooling Number of rotations Air flow (r.p.m.) 1670 „ Heating Number of rotations Air flow (r.p.m.) 1470 „ „ MODEL : AOG12LMCA „ Cooling Number of rotations Air flow (r.p.m.) 1830 1078 „...
  • Page 48 „ „ MODEL : AOG14LMCA „ Cooling Number of rotations Air flow (r.p.m.) 1940 1141 „ Heating Number of rotations Air flow (r.p.m.) 1700 1000 - (02 - 13) -...
  • Page 49: Operation Noise (Sound Pressure)

    NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency,Hz Octave band center frequency,Hz „ „ MODEL : AOG09LMCA „ „ Cooling Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40...
  • Page 50 „ „ MODEL : AOG12LMCA „ „ Cooling Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency,Hz Octave band center frequency,Hz „...
  • Page 51: Sound Level Check Point

    8-2. SOUND LEVEL CHECK POINT Air flow - (02 - 16) -...
  • Page 52: Electrical Characteristics

    ELECTRICAL CHARACTERISTICS Model name AOÛG07LMCA AOÛG09LMCA AOÛG12LMCA AOÛG14LMCA Voltage 230 ~ Power supply Frequency Max. operating current *1 10.5 Starting current Circuit breaker current Wiring spec. *2 Power cable *1: The maximum current is the total current of indoor unit and outdoor unit.
  • Page 53: Safety Devices

    SAFETY DEVICES Model Protection form AOÛG07LMCA AOÛG09LMCA AOÛG14LMCA AOÛG12LMCA 250V 20A Current fuse Circuit protection (Main printed circuit board) 250V 3.15A 250V 5A OFF: 100 ± 15 °C OFF: 150 ± 15 °C Fan motor protection Terminal protection program ON: 95 ± 10 °C ON: 120 ±...