Fujitsu AS G07KGTA Series Service Instruction page 40

Split type room air conditioner, wall mounted type inverter
Table of Contents

Advertisement

Trouble shooting 11
INDOOR UNIT Error Method:
Indoor unit power supply error for
fan motor
Detective Actuators:
Indoor Unit Controller PCB
Forecast of Cause :
1. External cause
Check Point 1 : Check external cause at lndoor and Outdoor (Voltage drop or Noise)
Instant drop : Check if there is a large load electric apparatus in the same circuit.
Momentary power failure : Check if there is a defective contact or leak current
Noise : Check if there is any equipment causing harmonic wave near electric line.
(Neon bulb or electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
OK
Check Point 2 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OK
Check Point 3 : Replace Controller PCB
If Check Point 1, 2 do not improve the symptom, replace Controller PCB.
Indicate or Display:
Outdoor Unit : No indication
Indoor Unit
ERROR CODE : [E : 39 ]
Detective details:
When a momentary power cut off.
When do not start fan motor.
2. Connection of connector failure
in the power supply circuit.
: Operation lamp: 3 time Flash, Timer lamp: 9 time Flash
Economy lamp: Continuous flash.
3. Controller PCB failure
02-14