Fujitsu AS G07KGTA Series Service Instruction

Split type room air conditioner, wall mounted type inverter

Advertisement

SERVICE
INSTRUCTION
SPLIT TYPE
ROOM AIR CONDITIONER
WALL MOUNTED
Models
Models
INVERTER
Indoor unit
Outdoor unit
AS*G07KGTA
AO*G07KGCA
AS*G09KGTA
AO*G09KGCA
AS*G12KGTA
AO*G12KGCA
AO*G14KGCA
AS*G14KGTA
ROG07KGCA
RSG07KGTA
ROG09KGCA
RSG09KGTA
ROG12KGCA
RSG12KGTA
ROG14KGCA
RSG14KGTA
type

Advertisement

Table of Contents
loading

Summary of Contents for Fujitsu AS G07KGTA Series

  • Page 1 SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED type INVERTER SERVICE INSTRUCTION Models Models Indoor unit Outdoor unit AS*G07KGTA AO*G07KGCA AS*G09KGTA AO*G09KGCA AS*G12KGTA AO*G12KGCA AO*G14KGCA AS*G14KGTA ROG07KGCA RSG07KGTA ROG09KGCA RSG09KGTA ROG12KGCA RSG12KGTA ROG14KGCA RSG14KGTA...
  • Page 2: Table Of Contents

    CONTENTS 1. DESCRIPTION OF EACH CONTROL OPERATION 1. COOLING OPERATION....................01-01 2. HEATING OPERATION....................01-02 3. DRY OPERATION......................01-03 4. AUTO CHANGEOVER OPERATION................01-04 5. INDOOR FAN CONTROL....................01-05 6. OUTDOOR FAN CONTROL..................01-07 7. LOUVER CONTROL..................... 01-08 8. COMPRESSOR CONTROL..................01-09 9.
  • Page 3 3. APPENDING DATA 3-1 FUNCTION SETTING....................03-01 3-1-1 INDOOR UNIT....................03-01 3-1-2 Procedures to change the Function Setting for wireless RC......03-05 3-2 Thermistor Resistance Values..................03-07 3-2-1 INDOOR UNIT....................03-07 3-2-2 OUTDOOR UNIT....................03-07...
  • Page 4: Description Of Each Control Operation

    WALL MOUNTED type INVERTER 1 . DESCRIPTION OF EACH CONTROL OPERATION...
  • Page 5: Cooling Operation

    1. COOLING OPERATION A sensor (room temperature thermistor) built in the indoor unit body will usually perceive difference or variation between a set temperature and present room temperature, and controls the operation frequency of the compressor. * If the room temperature is 6°C higher than a set temperature, the compressor operation frequency will attain to maximum performance.
  • Page 6: Heating Operation

    2. HEATING OPERATION A sensor (room temperature thermistor) built in the indoor unit body will usually perceive difference or variation between a set temperature and present room temperature, and controls the operation frequency of the compressor. * If the room temperature is lower by 6°C than a set temperature, the compressor operation frequency will attain to maximum performance.
  • Page 7: Dry Operation

    3. DRY OPERATION The compressor frequency shall change according to the temperature, set temperature, and room temperature variation which the room temperature sensor of the indoor unit body has detected as shown in the Table 4. ( Table 4 : Compressor frequency in Dry mode) Operating frequency X zone...
  • Page 8: Auto Changeover Operation

    4. AUTO CHANGEOVER OPERATION When the air conditioner is set to the AUTO mode by remote control, operation starts in the optimum mode from among the Heating, Cooling, and Monitoring modes. During operation, the optimum mode is automatically switched in accordance with temperature changes. °...
  • Page 9: Indoor Fan Control

    5. INDOOR FAN CONTROL 1. Fan speed ( Table 5 : Indoor fan speed ) Speed (rpm) Operation mode Air flow mode AS*G07KGTA AS*G09KGTA AS*G12KGTA AS*G14KGTA Powerful 1200 1230 1290 1330 Heating 1130 1160 1220 1260 1040 1070 1140 1160 1060 1080 Quiet...
  • Page 10 5. HEATING OPERATION Switch the airflow [Auto], and the indoor fan motor will run according to a room temperature, as shown in Fig. 5 On the other hand, if switched in [Hi] [Quiet], the indoor motor will run at a constant airflow of [Heat] operation modes Quiet, Lo, Me, High, as shown in Table 5.
  • Page 11: Outdoor Fan Control

    6. OUTDOOR FAN CONTROL 1. Outdoor Fan Motor Following table shows the type of the outdoor fan motor. The control method is different between AC motor and DC motor. ( Table 7 : Type of Motor ) AC Motor DC Motor 2.
  • Page 12: Louver Control

    7. LOUVER CONTROL 1. VERTICAL LOUVER CONTROL Fig.9 : Air Direction Range (Function Range) Each time the button is pressed, the air direction range will change as follow: Types of Air flow Direction Setting: ALL MODE : The Remote Controller's display does not change. Use the air direction adjustments within the ranges shown above.
  • Page 13: Compressor Control

    8. COMPRESSOR CONTROL 1. OPEARTION FREQUENCY RANGE The operation frequency of the compressor is different based on the operation mode as shown in the Table 11. (Table 11 : Compressor frequency range) Cooling / Dry Heating Minimum Maximum Minimum Maximum AO*G07KGCA 62rps AO*G09KGCA...
  • Page 14: Timer Operation Control

    9. TIMER OPEARTION CONTROL 9-1 WIRELESS REMOTE CONTROLLER The Table 13 shows the available timer setting based on the product model. ( Table 13 : Timer Setting ) ON TIMER / OFF TIMER PROGRAM TIMER SLEEP TIMER WEEKLY TIMER 1. OPEARTION FREQUENCY RANGE OFF timer : When the clock reaches the set time, the air conditioner will be turned off.
  • Page 15 3. SLEEP TIMER If the sleep is set, the room temperature is monitored and the operation is stopped automatically. If the operation mode or the set temperature is change after the sleep timer is set, the operation is continued according to the changed setting of the sleep timer from that time ON. In the cooling operation mode When the sleep timer is set, the setting temperature is increased 1°C.
  • Page 16 9-2 WIRED REMOTE CONTROLLER (OPTION) The table13 shows the available timer setting based on the product model. ( Table13 : Timer Setting ) ON TIMER / OFF TIMER WEEKLY TIMER DAY OFF ON TIMER / OFF TIMER Same to 9-1 1. ON TIMER / OFF TIMER and shown in those. WEEKLY TIMER This timer function can set operation times of the each day of the week.
  • Page 17: Electronic Expansion Valve Control

    10. ELECTRONIC EXPANSION VALVE CONTROL The most proper opening of the electronic expansion valve is calculated and controlled under the present operating condition based on the Table15. The compressor frequency, the detected temperature by the discharge temperature sensor, the indoor heat exchanger sensor, the outdoor heat exchanger sensor, and the outdoor temperature sensor. ( Table15 : The pulse range of the electronic expansion valve control ) Operation mode Pulse range...
  • Page 18: Auto Restart

    14. AUTO RESTART When the power was interrupted by a power failure, etc. during operation, the operation contents at that time are memorized and when power is recovered, operation is automatically started with the memorized operation contents. When the power is interrupted and recovered during timer operation, since the timer operation time is shifted by the time the power was interrupted, an alarm is given by blinking (7 sec ON/2 sec OFF) the indoor unit body timer lamp.
  • Page 19: Compressor Preheating

    17. COMPRESSOR PREHEATING When the outdoor heat exchanger temperature is lower than -4°C and the heating operation has been stopped for 30 minutes, power is applied to the compressor and the compressor is heated. (By heating the compressor, warm air is quickly discharged when operation is started.) When operation was started, and when the outdoor temperature rises to -2°C or greater, preheating is ended.
  • Page 20: Outdoor Unit Low Noise Operation

    21. OUTDOOR UNIT LOW NOISE OPERATION The OUTDOOR UNIT LOW NOISE Operation functions by pressing OUTDOOR UNIT LOW NOISE button on the remote controller. This operation stops the PFC control, and changes the Current release operation/release value. OUTDOOR UNIT LOW NOISE Operation mode can be used during cooling, heating and automatic operation. It can not be used in Fan and Dry mode ( Table 21 ) Control / Release...
  • Page 21: Defrost Operation Control

    23. DEFROST OPERATION CONTROL 1. CONDITION OF STARTING THE DEFROST OPERATION The defrost operation starts when the outdoor heat exchanger temperature sensor (Tn) detects the temperature lower than the values shown in Table19. ( Table 19 : Condition of starting Defrost Operation ) Compressor integrating operation time time defrosting after starting operation...
  • Page 22 3. Defrost Flow Chart The defrosting shall proceed by the integrating operation time, outdoor temperature and outdoor heat exchanger temperature as follows. Heating operation start : Compressor ON (Not defrosted for 10 minutes) 1st defrost 2nd and later defrost Integrating defrost (Constant monitoring) Compressor Compressor...
  • Page 23: Off Defrost Operation Control

    24. OFF DEFROST OPEARTION CONTROL When operation stops in the [Heating operation] mode, if frost is adhered to the outdoor unit heat exchanger, the defrost operation will proceed automatically. In this time, if indoor unit operation lamp flashes slowly (7 sec ON / 2 sec OFF), the outdoor unit will allow the heat exchanger to defrost, and then stop.
  • Page 24: Various Protections

    25. VARIOUS PROTECTIONS 1. DISCHARGE GAS TEMPERATURE OVERRISE PREVENSION CONTROL The discharge gas thermosensor (discharge thermistor : Outdoor side) will detect discharge gas temperature. When the discharge temperature becomes higher than Temperature , the compressor frequency is decreased 20rps, and it continues to decrease the frequency for 20rps every 120 seconds until the temperature becomes lower than Temperature .
  • Page 25 3. ANTIFREEZING CONTROL (Cooling and Dry mode) The compressor frequency is decrease on cooling & dry mode when the indoor heat exchanger temperature sensor detects the temperature lower than Temperature . Then, the anti-freezing control is released when it becomes higher than Temperature . (Table 27 : Anti-freezing Protection Operation / Release Temperature) Outdoor temperature Temperature...
  • Page 26: Trouble Shooting

    WALL MOUNTED type INVERTER 2 . TROUBLE SHOOTING...
  • Page 27: Error Display

    2-1 ERROR DISPLAY 2-1-1 INDOOR UNIT AND WIRED REMOTE CONTROLLER DISPLAY Please refer the flashing pattern as follows. Indoor Unit : AS*G07/ 09/ 12/ 14KGTA The OPERATION, TIMER and ECONOMY lamps operate as follows according to the error contents. Indoor Unit Display Wired Remote Trouble Controller...
  • Page 28 Indoor Unit Display Wired Remote Trouble Controller shooting Error Contents ECONOMY OPERATION TIMER Display (Green) (Orange) (Green) Current Sensor Error 8 times 4 times Continuous Over Current Error 9 times 4 times Continuous Compressor Control Error 9 times 5 times Continuous Continuous Outdoor Unit Fan Motor Error...
  • Page 29: Wired Remote Controller Display (Option)

    2-1-2 WIRED REMOTE CONTROLLER DISPLAY (OPTION) 2-Wire 1. Check the error 1. If an error occurs, an error icon appears on the “Monitor mode screen”. Touch the [Status] on the “Monitor mode screen”.The “Status” screen is displayed. 2. Touch the [Error Information] on the “Status”screen. The “Error Information”screen is displayed. (If there are no errors, the [Error Information] will not be displayed.) 3.
  • Page 30: Trouble Shooting With Error Code

    2-2 TROUBLE SHOOTING WITH ERROR CODE Trouble shooting 1 Indicate or Display: OUTDOOR UNIT Error Method: Outdoor Unit : No indication Indoor Unit : Operation lamp: 1 time Flash, Timer lamp: 1 time Flash Serial communication error Economy lamp: Continuous flash. (Serial Reverse Transfer Error) ERROR CODE : [E : 11 ] Detective details:...
  • Page 31 Indicate or Display: Trouble shooting 2 INDOOR UNIT Error Method: Outdoor Unit : No indication Indoor Unit : Operation lamp: 1 time Flash, Timer lamp: 1 time Flash Serial communication error Economy lamp: Continuous flash. (Serial Forward Transfer Error) ERROR CODE : [E : 11 ] Detective details: Detective Actuators: When the outdoor unit cannot receive the serial signal from Indoor unit...
  • Page 32 Indicate or Display: Trouble shooting 3 INDOOR UNIT Error Method: Outdoor Unit : No indication Indoor Unit : Operation lamp: 1 time Flash, Timer lamp: 8 time Flash External communication error Economy lamp: Continuous flash. ERROR CODE : [E : 18 ] Detective Actuators: Detective details: After receiving a signal from the external I/O PCB,...
  • Page 33 Indicate or Display: Trouble shooting 4 INDOOR UNIT Error Method: Outdoor Unit : No indication Indoor Unit : Operation lamp: 2 time Flash, Timer lamp: 2 time Flash Indoor unit capacity error Economy lamp: Continuous flash. ERROR CODE : [E : 22 ] Detective Actuators: Detective details: When the total capacity of indoor units does not match...
  • Page 34 Indicate or Display: Trouble shooting 5 INDOOR UNIT Error Method: Outdoor Unit : No indication Indoor Unit : Operation lamp: 2 time Flash, Timer lamp: 3 time Flash Combination error Economy lamp: Continuous flash. ERROR CODE : [E : 23 ] Detective Actuators: Detective details: Indoor unit...
  • Page 35 Indicate or Display: Trouble shooting 6 INDOOR UNIT Error Method: Outdoor Unit : No indication Indoor Unit : Operation lamp: 2 time Flash, Timer lamp: 6 time Flash Indoor unit address setting error Economy lamp: Continuous flash. ERROR CODE : [E : 26 ] Detective details: Detective Actuators: When the address number set by auto setting and manual setting are mixed in...
  • Page 36 Indicate or Display: Trouble shooting 7 INDOOR UNIT Error Method: Outdoor Unit : No indication Indoor Unit : Operation lamp: 2 time Flash, Timer lamp: 9 time Flash Connection unit number error (Indoor Economy lamp: Continuous flash. unit Wired remote controller error) ERROR CODE : [E : 29 ] Detective details: Detective Actuators:...
  • Page 37 Indicate or Display: Trouble shooting 8 INDOOR UNIT Error Method: Outdoor Unit : No indication Indoor Unit : Operation lamp: 3 time Flash, Timer lamp: 2 time Flash Indoor unit main PCB error Economy lamp: Continuous flash. ERROR CODE : [E : 32 ] Detective details: Detective Actuators: When power is on and there is some below case.
  • Page 38 Indicate or Display: Trouble shooting 9 INDOOR UNIT Error Method: Outdoor Unit : No indication Indoor Unit : Operation lamp: 3 time Flash, Timer lamp: 3 time Flash Indoor unit motor electricity Economy lamp: Continuous flash. consumption detection error ERROR CODE : [E : 33 ] Detective details: Detective Actuators: Indoor unit motor electricity...
  • Page 39 Indicate or Display: Trouble shooting 10 Outdoor Unit : No indication INDOOR UNIT Error Method: Indoor Unit : Operation lamp: 3 time Flash, Timer lamp: 5 time Flash Manual auto switch Error Economy lamp: Continuous flash. ERROR CODE : [E : 35 ] Detective Actuators: Detective details: Indoor unit Controller PCB...
  • Page 40 Indicate or Display: Trouble shooting 11 INDOOR UNIT Error Method: Outdoor Unit : No indication Indoor Unit : Operation lamp: 3 time Flash, Timer lamp: 9 time Flash Indoor unit power supply error for Economy lamp: Continuous flash. fan motor ERROR CODE : [E : 39 ] Detective Actuators: Detective details:...
  • Page 41 Trouble shooting 12 Indicate or Display: INDOOR UNIT Error Method: Outdoor Unit : No indication Indoor Unit : Operation lamp: 3 time Flash, Timer lamp: 10 time Flash Indoor unit Communication circuit Economy lamp: Continuous flash. (wired remote controller) error ERROR CODE : [E : 3A ] Detective details: Detective Actuators:...
  • Page 42 Indicate or Display: Trouble shooting 13 INDOOR UNIT Error Method: Outdoor Unit : No indication Indoor Unit : Operation lamp: 4 time Flash, Timer lamp: 1 time Flash Indoor Room Thermistor Error Economy lamp: Continuous flash. ERROR CODE : [E : 41 ] Detective details: Detective Actuators: Indoor unit Controller PCB...
  • Page 43 Indicate or Display: Trouble shooting 14 INDOOR UNIT Error Method: Outdoor Unit : No indication Indoor Unit : Operation lamp: 4 time Flash, Timer lamp: 2 time Flash Indoor Heat Ex. Thermistor Error Economy lamp: Continuous flash. ERROR CODE : [E : 42 ] Detective Actuators: Detective details: Indoor unit Controller PCB...
  • Page 44 Trouble shooting 15 Indicate or Display: INDOOR UNIT Error Method: Outdoor Unit : No indication Indoor Unit : Operation lamp: 5 time Flash, Timer lamp: 1 time Flash Indoor Unit Fan Motor Error Economy lamp: Continuous flash. ERROR CODE : [E : 51 ] Detective Actuators: Detective details: Indoor unit Controller PCB...
  • Page 45 Indicate or Display: Trouble shooting 16 OUTDOOR UNIT Error Method: Outdoor Unit : No indication Indoor Unit : Operation lamp: 6 time Flash, Timer lamp: 2 time Flash Economy lamp: Continuous flash. Outdoor unit main PCB error ERROR CODE : [E : 62 ] Detective Actuators: Detective details: Access to EEPROM failed due to some cause after outdoor unit started.
  • Page 46 Indicate or Display: Trouble shooting 18 Outdoor Unit : No indication OUTDOOR UNIT Error Method: INDOOR UNIT Indoor Unit : Operation lamp: 6 time Flash, Timer lamp: 4 time Flash PFC circuit error Economy lamp: Continuous flash. ERROR CODE : [E : 64 ] Detective Actuators: Detective details: When inverter output DC voltage is higher than 415V for over 3 seconds,...
  • Page 47 Indicate or Display: Trouble shooting 19 OUTDOOR UNIT Error Method: Outdoor Unit : No indication Indoor Unit : Operation lamp: 6 time Flash, Timer lamp: 5 time Flash IPM Error Economy lamp: Continuous flash. ERROR CODE : [E : 65 ] Detective details: Detective Actuators: When more than normal operating current to IPM in Main PCB flows,...
  • Page 48 Indicate or Display: Trouble shooting 21 OUTDOOR UNIT Error Method: Outdoor Unit : No indication Indoor Unit : Operation lamp: 7 time Flash, Timer lamp: 1 time Flash Discharge Thermistor Error Economy lamp: Continuous flash. ERROR CODE : [E : 71 ] Detective details: Detective Actuators: When Discharge pipe temperature thermistor open or short-circuit...
  • Page 49 Indicate or Display: Trouble shooting 22 OUTDOOR UNIT Error Method: Outdoor Unit : No indication Indoor Unit : Operation lamp: 7 time Flash, Timer lamp: 3 time Flash Heat Ex. Liquid Outlet Economy lamp: Continuous flash. Thermistor Error ERROR CODE : [E : 73 ] Detective details: Detective Actuators: Outdoor unit Main PCB...
  • Page 50 Indicate or Display: Trouble shooting 23 Outdoor Unit : No indication OUTDOOR UNIT Error Method: Indoor Unit : Operation lamp: 7 time Flash, Timer lamp: 4 time Flash Outdoor Thermistor Error Economy lamp: Continuous flash. ERROR CODE : [E : 74 ] Detective details: Detective Actuators: Outdoor unit Main PCB...
  • Page 51 Indicate or Display: Trouble shooting 24 OUTDOOR UNIT Error Method: Outdoor Unit : No indication Indoor Unit : Operation lamp: 8 time Flash, Timer lamp: 4 time Flash Current Sensor Error Economy lamp: Continuous flash. ERROR CODE : [E : 84 ] Detective Actuators: Detective details: When Input Current Sensor has detected 0A, while Inverter Compressor is...
  • Page 52 Indicate or Display: Trouble shooting 25 OUTDOOR UNIT Error Method: Outdoor Unit : No indication Indoor Unit : Operation lamp: 9 time Flash, Timer lamp: 4 time Flash Over Current Error Economy lamp: Continuous flash. ERROR CODE : [E : 94 ] Detective details: Detective Actuators: "Protection stop by overcurrent generation after inverter compressor start...
  • Page 53 Indicate or Display: Trouble shooting 26 OUTDOOR UNIT Error Method: Outdoor Unit : No indication Indoor Unit : Operation lamp: 9 time Flash, Timer lamp: 5 time Flash Compressor Control Error Economy lamp: Continuous flash. ERROR CODE : [E : 95 ] Detective details: Detective Actuators: If the detected rotor location is out of phase with actual rotor location...
  • Page 54 Indicate or Display: Trouble shooting 27 OUTDOOR UNIT Error Method: Outdoor Unit : No indication Indoor Unit : Operation lamp: 9 time Flash, Timer lamp: 7 time Flash Outdoor Unit Fan Motor Error Economy lamp: Continuous flash. ERROR CODE : [E : 97 ] Detective Actuators: Detective details: When outdoor fan rotation speed is less than 100rpm in 20 seconds...
  • Page 55 Indicate or Display: Trouble shooting 28 OUTDOOR UNIT Error Method: Outdoor Unit : No indication Indoor Unit : Operation lamp: 9 time Flash, Timer lamp: 9 time Flash 4-Way Valve Error Economy lamp: Continuous flash. ERROR CODE : [E : 99 ] Detective Actuators: Detective details: When the indoor heat exchanger temperature is compared with...
  • Page 56 Indicate or Display: Trouble shooting 29 OUTDOOR UNIT Error Method: Outdoor Unit : No indication Indoor Unit : Operation lamp: 10 time Flash, Timer lamp: 1 time Flash Discharge Temp. Error Economy lamp: Continuous flash. ERROR CODE : [E : A1 ] Detective details: Detective Actuators: Outdoor unit Main PCB...
  • Page 57: Trouble Shooting With No Error Code

    2-3 TROUBLE SHOOTING WITH NO ERROR CODE Forecast of Cause: Trouble shooting 30 1. Power supply failure 2. External cause Indoor Unit - No Power 3. Electrical components defective Check Point 1 : Check Installation Condition Isn’t the breaker down? Check loose or removed connection cable.
  • Page 58 Forecast of Cause: Trouble shooting 31 1. Power supply failure 2. External cause Outdoor Unit - No Power 3. Electrical Components defective Check Point 1 : Check Installation Condition Isn’t the breaker down? Check loose or removed connection cable. >>If abnormal condition is found, correct it by referring to Installation Manual or Data &...
  • Page 59 Forecast of Cause: Trouble shooting 32 1. Setting/ Connection failure 2. External cause No Operation (Power is ON) 3. Electrical Component defective Check Point 1 : Check indoor and outdoor installation condition Indoor Unit - Check incorrect wiring between Indoor Unit - Remote Control. Or, check if there is an open cable connection.
  • Page 60 Forecast of Cause: Trouble shooting 33 1. Indoor Unit error 2. Outdoor Unit error No Cooling / No Heating 3. Effect by surrounding environment 4. Connection pipe / Connection wire failure 5. Refrigeration cycle failure Check Point 1 : Check Indoor unit Does Indoor unit Fan run on High fan? Is Air filter dirty? Is Heat exchanger clogged?
  • Page 61 Forecast of Cause : Trouble shooting 34 1. Abnormal installation (Indoor/ Outdoor) Abnormal Noise 2. Fan failure (Indoor/ Outdoor) 3. Compressor failure (Outdoor) Diagnosis method when abnormal noise is occurred Abnormal noise is coming from Indoor unit. Abnormal noise is coming from Outdoor unit. (Check and correct followings) (Check and correct followings) Is Main unit installed in stable condition?
  • Page 62: Service Parts Information

    2-4 SERVICE PARTS INFORMATION SERVICE PARTS INFORMATION 1 Compressor Diagnosis method of Compressor ( If Outdoor Unit LED displays Error, refer to Trouble shooting ) Abnormal noise Stops soon after starting up Does not start up Check if vibration noise by Is there open or loose connection Is there open or loose connection loose bolt or contact noise...
  • Page 63 SERVICE PARTS INFORMATION 2 Inverter Compressor Check Point 1 : Check Connection Check terminal connection of Compressor (loose or incorrect wiring) Terminal cover opened (BLACK) U(R) V(S) (RED) (WHITE) Check Point 2 : Check Winding Resistance Check winding resistance of each terminal If the resistance value is 0 or infinite, replace Compressor.
  • Page 64 SERVICE PARTS INFORMATION 3 Outdoor unit Electronic Expansion Valve ( EEV ) Check Point 1 : Check Connections Check connection of connector (P30) ( Loose connector or open cable ) EXPANSION VALVE COIL BLUE ORANGE YELLOW WHITE Check Point 2 : Check Coil of EEV Check Point 3 : Check Voltage from Main PCB.
  • Page 65 SERVICE PARTS INFORMATION 4 Indoor unit fan motor Check Point 1 : Check rotation of Fan Rotate the fan by hand when operation is off. (Check if fan is caught, dropped off or locked motor) >>If Fan or Bearing is abnormal, replace it. Check Point 2 : Check resistance of Indoor Fan Motor Refer to below.
  • Page 66: Appending Data

    WALL MOUNTED type INVERTER 3 . APPENDING DATA...
  • Page 67: Function Setting

    3-1. FUNCTION SETTING 3-1-1 INDOOR UNIT Remote controller address setting * Because this setting is normally done automatically when 2-wire-type wired remote controller is installed, setting is unnecessary. Multiple indoor units can be operated by using one wired remote controller. Set the unit number of each indoor unit.
  • Page 68 Room temperature control for indoor unit sensor Depending on the installed environment, correction of the room temperature sensor may be re- quired. Select the appropriate control setting according to the installed environment. The temperature correction values show the difference from the Standard setting "00" (manufactur- er’s recommended value).
  • Page 69 Auto restart Enables or disables automatic restart after a power interruption. Function number Setting value Setting description Factory setting ♦ *Auto restart is an emergency function such as for power outage etc. Do not attempt to use this function in normal operation. Be sure to operate the unit by remote controller or external device.
  • Page 70 Indoor unit fan control for energy saving for cooling Enables or disables the power-saving function by controlling the indoor unit fan rotation when the outdoor unit is stopped during cooling operation. Function number Setting value Setting description Factory setting l l o ♦...
  • Page 71: Procedures To Change The Function Setting For Wireless Rc

    3-1-2 Procedures to change the Function Setting for wireless RC This procedure changes to the function settings used to control the indoor unit according to the installation conditions. Incorrect settings can cause the indoor unit malfunction. After the power is turned on, perform the "FUNCTION SETTING" according to the installation conditions using the remote controller.
  • Page 72 Selecting the Remote Controller Signal Code (1) Press the START/STOP( ) button until only the clock is displayed on the remote controller display. (2) Press the MODE button for at least 5 seconds to display the current signal code. (initially set to (3) Press the SET TEMP.( ) ( ) buttons to change the signal code between Match the code on the display to the air conditioner signal code.
  • Page 73: Thermistor Resistance Values

    3-2. Thermistor Resistance Values 3-2-1 INDOOR UNIT Room temperature thermistor Indoor heat exchanger thermistor Temp ( C) Resistance(k ) Voltage(V) Temp ( C) Resistance(k ) Voltage(V) -10.0 58.2 0.73 -30.0 1131.9 0.21 -5.0 44.0 0.93 -25.0 804.5 0.29 33.6 1.15 -20.0 579.6 0.40...
  • Page 74 3-3-17,Suenaga,Takatsu-ku,Kawasaki 213-8502,Japan Sep. 2017 Printed in Japan...