Signal Connections; Alarm Outputs; Alarm Inputs; System Communications Ports - GE Integritas 3TL125-SACY-D10Y-P000 Quick Start Manual

Wall mount 3 rectifier battery charger
Table of Contents

Advertisement

Information: Signal Connections.
Alarm Relays Factory set to Open On Alarm. Rated 125V (60V for 24V and 48V chargers), 0.5A.
"Dry" No Voltage Binary Inputs Require a contact closure to Common (pin 2).
"Dry" 24V Biased Binary inputs Require a contact closure to 24V Source (pin 2).
Connector
Description—Signal on Pin 1
TB1
Power Critical Alarm
TB2
Power Major Alarm
TB3
Power Minor Alarm
TB4
Alarm R1 (default is RFA/MRFA)
TB5
Alarm R2 (default is ACFMACF)
TB6
Alarm R3 (default is BD/VLV)
TB7
Alarm R4 (default is GFI)
TB8
Alarm R5 (default is SPD, DC, and AC)
TB9
Alarm R6 (default is BTA "Battery Test Active")
TB10
Alarm R7 (default is "Check Battery")
Connector
Description—Signal on Pin 1
TB11
"Dry" No Voltage Binary contact input (default is AUX1 "Air Conditioner Fail")
(IN007)
TB12
"Dry" No Voltage Binary contact input (default is AUX2 "Door Open")
(IN008)
TB13
"Dry" No Voltage Binary contact input (default AUX3 "High External Ambient")
(IN009)
TB14
"Dry" No Voltage Binary contact input (default AUX4 "Low External Ambient")
(IN010)
TB15
"Dry" No Voltage Binary contact input (default "Plant Battery Test (PBT)")
(IN006)
TB16
"Dry" No Voltage Binary contact input (default "Remote Rectifier Standby/Emergency Power
(IN005)
Off")
TB17
"Dry" 24V Biased Binary contact input 24V Source (default "AUX9 Auxiliary 9")
(IN001)
TB18
"Dry" 24V Biased Binary contact input (default AUX8, "Auxiliary 8")
(IN002)
TB19
"Dry" 24V Biased Binary contact input 24V Source (default OSA1, "Open String")
(IN004)
TB20
"Dry" 24V Biased Binary contact input (default AUX6, "Hydrogen Present")
(IN003)
TB21
+24V Alternative external 24VDC back bias input for controller.
Connector
Description—Signal on Pin 1
RECT DATA
Connection to isolated rectifier RS485 Galaxy protocol serial bus.
1-WIRE DA-
Connection to 1-Wire temperature probes. 1-Wire signal on pin 1.
TA
18

Alarm Outputs

Alarm Inputs

System Communications Ports

Integritas Wall Mount Charger - Quick Start Guide
Document 8600092587P r03 2018 August
Pin 2
Common
Common
Common
Common
Common
Common
Common
Common
Common
Common
Pin 2
No Voltage Re-
turn
No Voltage Re-
turn
No Voltage Re-
turn
No Voltage Re-
turn
No Voltage Re-
turn
No Voltage Re-
turn
24V Source
24V Source
24V Source
24V Source
+24V DC Return
Pin 2
not applicable
1-Wire Return

Advertisement

Table of Contents
loading

Table of Contents