Step 3—Ground the Chassis
Chassis Ground lug - 1/4" on 5/8" centers (lug provided).
Minimum 6 AWG recommended.
1. Connect ground wire to chassis on top or bottom of cabinet.
1/4-20 screws (2) provided
Torque to 65 in-lb (7.3 Nm) - 7/16" socket.
Step 4—Connect AC Input
AC Input Box location:
Bottom Feed—bottom left
AC knockouts: for 2" conduit.
Danger:
Shock Hazard—Turn OFF and lock-out tag-out the AC source before making AC connections.
When connecting to AC mains, follow all local and national wiring rules.
Bottom Feed
Terminal Block for Single AC Feed shown
Caution: Ensure that wires do not come in contact with sharp or rough surfaces that may damage insulation and cause a short circuit.
1. Verify all AC breakers are off—Charger AC1 and external AC feed breaker.
2. Choose the next step to match AC input voltage marked on the charger ratings label.
AC Input per Charger Label
120/240
200/240
6
Top Feed—top left
Screw
Wire Entry
Ground
Bar
Ground
Wire Lug
Screw
AC Input Option
AC
AC
Integritas Wall Mount Charger - Quick Start Guide
Document 8600092587P r03 2018 August
Chassis Ground Lug
(top or bottom)
Top Feed
Terminal Block for Single AC Feed shown
Follow Step
Step 4A Single Phase
Step 4B 3 Phase