Step 13—Apply Power to Loads and Batteries Connected through Breakers
Rectifiers are keyed allowing only their installation into chargers of the same voltage.
1. Turn on BATT breaker if present)
2. Verify DC output voltage with a meter on VDC+ and VDC– jacks on the Output Signal
Terminals voltage is output voltage ÷100.
3. Turn on load breaker(s) DC1 (and DC2 if present)
4. Verify No Ground Fault alarm—Ground Fault Unit U LED is Green and F LED NOT Red.
If F LED is Red, adjust values of resistance threshold down (R1 + R2).
Operate Test/Reset button after each adjustment.
If alarm continues, trouble shoot load and battery wiring accordingly.
Output Ground Fault Unit
Bottom Feed shown
Test/Reset Button
14
LEDs
Output Ground Fault Unit
Integritas Wall Mount Charger - Quick Start Guide
Document 8600092587P r03 2018 August