Information: Battery Monitoring Connections - for use with NiCd and Lead acid batteries (VRLA, Flooded)
Battery Monitoring is accomplished with a "Daisy Chained" series of probes. The Probes monitor battery temperature. Bolt the Probe under
the "–" terminal connector hardware; NOT under the connecting lug.
Max per system: Probes - 16.
Battery Temperature Measurement
Ordering Codes
Descriptions
1600093513A
DTP873-Battery Thermal Probe
1600093512A
DTP873-Ambient Probe
Information Interlock Cable Recommendations
Wire - 20-24 AWG
Mating Connector: Molex housing - 43025- 0200,
Terminals - Molex 43030-0008 (15µ"gold plated)
Hand Crimp Tool - Molex 0638190000
Insertion Tool - Molex 0638120800
Extraction Tool - Molex 0011030043