Alarm List During Pti - Daikin LXE10E-A14 Service Manual

Marine type container refrigeration unit
Table of Contents

Advertisement

https://daikin-p.ru
3.9.2.4 Alarm list during PTI (Pre-Trip Inspection)
The alarm during automatic PTI are concerned with PTI inspection items in addition to those during
normal operation.
The alarms at automatic PTI are indicated in J ※※※., being separated from those during normal
operation.
There are some alarms which are not displayed on the control panel, however, they can be checked
referring to the PTI report.
Check NO.
Check content
(LED display)
P00
Basic data
P02
All sensor
P04
Power supply
P05
Starting
P06
HPS
''
''
''
P08
Pump-down
P10
Liquid solenoid valve
P12
RS, SS accuracy
P14
HPT, LPT accuracy
P16
Evaporator fan motor
P20
Economizer solenoid valve
P22
Discharge gas by-pass solenoid valve J221
P24
Defrost solenoid valve
P26
Operation
P28
Suction modulating valve
P29
Electronic expansion valve
P30
Injection solenoid valve
P32
Hot-gas solenoid valve
Reheat coil solenoid valve
P50
Pull-down cooling capacity
P50
0˚C control
P60
0˚C control
P70
Defrosting
P80
Pull-down cooling capacity
P90
–18˚C control
Alarm Indication
(LED display)
No indication
Check basic-data
Same as normal operation Check basic-data
No indication
Check basic-data
J051
Compressor malfunction
J061
Abnormal OFF value
J062
Not recovered (Not reset)
J064
High pressure does not rise.
J065
High pressure does not drop.
J081
Long pump-down
J101
Valve leakage
J121
Sensor deterioration
J141
Sensor deterioration
J161
Evaporator fan motor malfunction
Economizer solenoid valve malfunction
J201
Discharge gas by-pass solenoid valve malfunction
J241
Defrost solenoid valve malfunction
No indication
Judged with P28
J281
Suction modulating valve does not activate
J291
Long pump-down
J301
Injection solenoid valve malfunction
J321
Hot-gas solenoid valve malfunction
J322
Reheat coil solenoid valve malfunction
J501
Out of ambient temperature conditions
J502
Long pull-down time
No indication
J701
Out of starting conditions
J702
Long defrosting time
No indication
J901
Long pull-down time
Refer to chapter 6.3 for more information.
3-58
Alarm content
S.PTI F.PTI
Remarks