Daikin LXE10E-A14 Service Manual page 24

Marine type container refrigeration unit
Table of Contents

Advertisement

https://daikin-p.ru
(1) Set point temperature and control sensor
When the set point temperature (referred to as SP hereafter) is –10.1˚C(+13.8˚F) or lower, the
compressor is operated ON and OFF, in response to return air temperature.
(2) Control
qWhen the control temperature reaches SP (point A), the
compressor and condenser fan are turned off after the liquid
solenoid valve has been de-energized and the pump down
operation has been completed.
wWhen the control temperature exceeds SP+1.0˚C, the compressor,
liquid solenoid valve and condenser fan are turned on.
However, the compressor runs for at least 2 minutes every
time once it is turned on. Even if the control temperature
becomes SP or lower (point C) within 2 minutes after the
compressor is turned on, the compressor, condenser fan
and liquid solenoid valve are not turned off. (2 minutes
compressor forced operation)
EV:Elec.Exp.Valve
LSV:Liquid Solenoid Valve
DSV:Defrost Solenoid Valve
ESV:Economizer Solenoid Valve
DPR:Discharge pressure regulator
SMV:Suction Modulation Valve
EV
Receiver
FROZEN (Return air < 5˚C)
HSV:Hot Gas Solenoid Valve
ISV:Injection Solenoid Valve
BSV:Discharge gas Bypass Solenoid Valve
LPT:Low Pressure Transducer
HPT:High Pressure Transducer
HPS:High Pressure Switch.
2-10
–10˚C
SP+2˚C
SP+1˚C
A
SP
SP–1˚C
SP–2˚C
C