2. General description

2.1 Main specifications

Item
Condenser cooling system
Controller
Power supply
Compressor
Evaporator
Air-cooled condenser
Evaporator fan
Evaporator fan motor
Condenser fan
Condenser fan motor
System
Initiation
Termination
Refrigerant flow control
Capacity control
Protective devices
/Safety devices
Refrigerant (charged amount)
Refrigerant oil (charged amount)
Weight
Model
Air cooled type
DECOS3C
AC 3-phase 380V/400V/415V 50Hz, 440V/460V 60Hz
Hermetic scroll type (Motor output: 5.5kW)
Cross fin coil type
Cross fin coil type
Propeller fan
Three-phase squirrel-cage induction motor
Propeller fan
Three-phase squirrel-cage induction motor
Hot-gas defrosting system
Dual timer, on-demand defrost and manual switch
Detecting the temperature of evaporator outlet pipe and return air
Electronic expansion valve
Capacity control with hot gas bypass and suction modulating valve
Circuit breaker, PT/CT board (for over current protection).
Compressor thermal protector
Condenser fan-motor thermal protector
Evaporator fan-motor thermal protector
High-pressure switch, Fusible plug, Fuse (10A, 5A)
R134a : 4.6 (kgf)
IDEMITSU, Daphne hermetic oil FVC 46D : 2.2(R)
LXE10E-A14 : 465(kgf)
LXE10E-A15 : 495(kgf)
2-1