7.2 Alarm table

pRack pR300T can manage both alarms relating to the status of the digital inputs and to system operation, similar to the pRack pR300. For each alarm, the
following are controlled:
The actions on the devices, if necessary
The output relays (one global and two with diff erent priorities, if confi gured)
The red LED on the terminal and the buzzer, where present
The type of acknowledgement (automatic, manual, semiautomatic)
Any activation delay
The complete list of alarms for the pRack pR300T with the related information as described above, is reported below.
Code
Description
ALA**
C.pCOe offl ine n° 001 Offl ine
ALA01
Discharge temperature probe malfunction
ALA02
Discharge temperature probe malfunction
ALA03
External temperature probe malfunction
ALA04
Generic probe malfunction A, PLB1
ALA05
Generic probe malfunction B, PLB1
ALA06
Generic probe malfunction C, PLB1
ALA07
Generic probe malfunction D, PLB1
ALA08
Generic probe malfunction E, PLB1
ALA09
Generic probe malfunction A, PLB2
ALA10
Generic probe malfunction B, PLB2
ALA11
Generic probe malfunction C, PLB2
ALA12
Generic probe malfunction D, PLB2
ALA13
Generic probe malfunction E, PLB2
ALA14
Generic probe malfunction A, PLB3
ALA15
Generic probe malfunction B, PLB3
ALA16
Generic probe malfunction C, PLB3
ALA17
Generic probe malfunction D, PLB3
ALA18
Generic probe malfunction E, PLB3
ALA19
Generic probe malfunction A, PLB4
ALA20
Generic probe malfunction B, PLB4
ALA21
Generic probe malfunction C, PLB4
ALA22
Generic probe malfunction D, PLB4
ALA23
Generic probe malfunction E, PLB4
ALA24
Suction pressure probe malfunction
ALA25
Suction temperature probe malfunction
ALA26
Room temperature probe malfunction
ALA27
Condensing pressure probe malfunction, line 2
ALA28
Discharge temperature probe malfunction, line 2
ALA29
Suction pressure probe malfunction, line 2
ALA30
Suction temperature probe malfunction, line 2
ALA31
Gall cooler backup pressure probe malfunction
ALA32
Condensing pressure backup probe malfunction, line 2
ALA33
Suction pressure backup probe malfunction
ALA34
Suction pressure backup probe malfunction, line 2
ALA35
Common oil temperature probe malfunction
ALA36
Common oil temperature probe malfunction, line 2
ALA39
Discharge temperature probe malfunction, compressors 1...6
ALA40
Discharge temperature probe malfunction, compressors 1...6, line 2
ALA41
Oil temperature probe malfunction, compressors 1...6, line 1
ALA42
Oil temperature probe malfunction, compressor 1, line 2
ALA43
Gas cooler output temperature probe malfunction
ALA44
CO2 receiver pressure probe malfunction
ALA45
Gas cooler output backup temperature probe malfunction
ALA55
Discharge probe malfunction, line 1
ALA56
Discharge probe malfunction, line 2
ALA57
High/low discharge pressure, line 1
ALA58
High/low discharge pressure, line 2
ALB01
Low suction pressure from pressure switch
ALB02
High condensing pressure from pressure switch
ALB03
Low gas cooler output temperature from probe
ALB04
High gas cooler output temperature from probe
ALB05
Liquid level
ALB06
Common oil diff erential
ALB07
Common fan circuit breaker
ALB08
Low suction pressure from pressure switch. line 2
ALB09
High condensing pressure from pressure switch. line 2
ALB10
Low condensing pressure from probe, line 2
ALB11
High condensing pressure from probe, line 2
ALB12
Liquid level, line 2
ALB13
Common oil diff erential, line 2
ALB14
Common fan circuit breaker, line 2
ALB15
High suction pressure from probe
ALB16
Low suction pressure from probe
ALB17
High suction pressure from probe, line 2
ALB18
Low suction pressure from probe, line 2
ALB21
Shutdown to prevent high pressure
ALB22
Shutdown to prevent high pressure, line 2
ALC90
L1 – Generic alarm comp.
ALC91
L1 – Compressors overload alarm
ALC92
L1 – Compressors high pressure
ALC93
L1 – Compressors low pressure
ALC94
L1 – Compressors oil alarm
ALC96
L2 – Compressors generic alarm
ALC97
L2 – Compressors overload alarm
ALC98
L2 – Compressors high pressure
ALC99
L2 – Compressors low pressure
ALC9a
L2 – Compressors oil alarm
Copyright HPL March 2021
Reset
Delay
Alarm relay
Automatic
0s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
Settable
Automatic
Settable
Semiautomatic
Confi g.
Man./Autom.
Confi g.
Automatic
Settable
Automatic
Settable
Automatic
Confi g.
Automatic
Confi g.
Automatic
Confi g.
Confi g.
Semiautomatic
Confi g.
Man./Autom.
Confi g.
Automatic
Confi g.
Automatic
Confi g.
Automatic
Confi g.
Automatic
Confi g.
Automatic
Confi g.
Confi g.
Automatic
Confi g.
Automatic
Confi g.
Automatic
Confi g.
Automatic
Confi g.
Manual
Confi g.
Manual
Confi g.
Man./Auto
confi g
Man./Auto
confi g
Man./Auto
confi g
Man./Auto
confi g
Man./Auto
confi g
Man./Auto
confi g
Man./Auto
confi g
Man./Auto
confi g
Man./Auto
confi g
Man./Auto
confi g
75
Page 124 of 169
Action
Outputs held in current status or according
R1
to pattern
R2
Related functions disabled
R1
Related functions disabled
R2
Related functions disabled
R2
Related functions disabled
R2
Related functions disabled
R2
Related functions disabled
R2
Related functions disabled
R2
Related functions disabled
R2
Related functions disabled
R2
Related functions disabled
R2
Related functions disabled
R2
Related functions disabled
R2
Related functions disabled
R2
Related functions disabled
R2
Related functions disabled
R2
Related functions disabled
R2
Related functions disabled
R2
Related functions disabled
R2
Related functions disabled
R2
Related functions disabled
R2
Related functions disabled
R2
Related functions disabled
R2
Related functions disabled
R1
Related functions disabled
R2
Related functions disabled
R2
Related functions disabled
R1
Related functions disabled
R2
Related functions disabled
R1
Related functions disabled
R2
Related functions disabled
R2
Related functions disabled
R2
Related functions disabled
R2
Related functions disabled
R2
Related functions disabled
R2
Related functions disabled
R2
Related functions disabled
R2
Related functions disabled
R2
Related functions disabled
R2
Related functions disabled
R2
Related functions disabled
R2
Related functions disabled
R2
Related functions disabled
R2
Related functions disabled
R2
Related functions disabled
R2
Related functions disabled
R1
-
R1
-
R1
Shutdown compressors
R1
Shutdown compressors
R1
Fan forcing at 0%
Fan forcing at 100% and shutdown
R1
compres.
R2
-
R2
-
-
R1
Shutdown compressors, line 2
R1
Shutdown compressors, line 2
R1
-
R1
-
R2
-
R2
-
-
R1
-
R1
-
R1
-
R1
-
R1
Shutdown compressors
R1
Shutdown compressors, line 2
confi g
Shutdown compressor with alarm
confi g
Shutdown compressor with alarm
confi g
Shutdown compressor with alarm
confi g
Shutdown compressor with alarm
confi g
Shutdown compressor with alarm
confi g
Shutdown compressor with alarm
confi g
Shutdown compressor with alarm
confi g
Shutdown compressor with alarm
confi g
Shutdown compressor with alarm
confi g
Shutdown compressor with alarm
P4367 Rev 01
pRack PR300T +0300018EN rel. 1.5 - 02.05.2017
ENG

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hubbard hcu-pxb1

Table of Contents