Checking Supply Air Cfm; Power Exhaust Specifications; Pressure Drop Across Coil - York International ZK Series Installation Manual

R-410a, 3 - 5 ton, 60 hertz
Table of Contents

Advertisement

Table 18: Power Exhaust Specifications
Model
Voltage
2PE04703725
208/230-1-60
2PE04703746
460-1-60
2PE04703758
575-3-60
1. Motors are multi-tapped and factory wired for high speed.

Checking Supply Air CFM

The RPM of the supply air blower will depend on the required
CFM, the unit accessories or options and the static resistances
of both the supply and the return air duct systems. With this
information, the motor speed tap (direct drive) or the motor
pulley number of turns open (belt drive) can be determined from
the Blower Performance Data Tables.
Belt drive blower systems MUST be adjusted to the
specific static and CFM requirements for the application.
The belt drive blowers are NOT set at the factory for any
specific static or CFM. Adjustments of the blower speed
and belt tension are REQUIRED. Tighten blower pulley
and motor sheave set screws after these adjustments.
Re-checking set screws after 10-12 hrs. run time is
recommended.
Note the following:
1.
The supply air CFM must be within the limitations shown in
the Unit Physical Data Table 8.
2.
Pulleys can be adjusted in half turn increments.
3.
The tension on the belt should be adjusted as shown in the
Belt Adjustment Figure 18.
4.
Tighten blower pulley and motor sheave set screws after
any adjustments. Re-check set screws after 10-12 hrs. run
time is recommended.
Start the supply air blower motor. Adjust the resistances in both
the supply and the return air duct systems to balance the air
distribution throughout the conditioned space. The job
specifications may require that this balancing be done by
someone other than the equipment installer.
To check the supply air CFM after the initial balancing has been
completed:
1.
Remove the two 5/16" dot plugs from the blower motor and
the filter access panels shown in Figure 8.
2.
Insert at least 8" of 1/4 inch tubing into each of these holes
for sufficient penetration into the air flow on both sides of
the indoor coil.
Johnson Controls Unitary Products
Motor
HP
RPM
QTY
1
1/2
1725
1
1
1/2
1725
1
1/2
1725
1
Motor
LRA
FLA
MCA
23.7
4.4
5.5
4.1
1.7
2.1
4.5
0.9
1.1
NOTE: The tubes must be inserted and held in a position
perpendicular to the air flow so that velocity pressure
will not affect the static pressure readings.
3.
Using an inclined manometer, determine the pressure drop
across a dry evaporator coil. Since the moisture on an
evaporator coil may vary greatly, measuring the pressure
drop across a wet coil under field conditions would be
inaccurate. To assure a dry coil, the compressors should
be deactivated while the test is being run.
4.
Knowing the pressure drop across a dry coil, the actual
CFM through the unit can be determined from the curve in
Pressure Drop vs. Supply Air CFM (Figure 20).
Failure to properly adjust the total system air quantity and
static pressure can result in extensive system damage.
After readings have been obtained, remove the tubes and
reinstall the two 5/16" dot plugs that were removed in Step 1.
NOTE: De-energize the compressors before taking any test
measurements to assure a dry indoor coil.
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0
0
500
1000 1500 2000 2500 3000 3500
Figure 20: Pressure Drop Across Coil
5121817-TIM-A-0515
Fuse
CFM @
Size
0.1 ESP
8
5
2
T05
T03
T04
NOMINAL CFM
1350
1350
1350
41