York International ZK Series Installation Manual page 20

R-410a, 3 - 5 ton, 60 hertz
Table of Contents

Advertisement

5121817-TIM-A-0515
ZKT03 Thru T05 Without Powered Convenience Outlet (Direct Drive)
Compressors
Size
(each)
Volt
(Tons)
RLA LRA
208-3-60 10.4
73
T03
(3.0)
230-3-60 10.4
73
208-3-60 13.7
83.1
T04
(4.0)
230-3-60 13.7
83.1
208-3-60
16
110
T05
(5.0)
230-3-60
16
110
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
20
OD Fan
Supply
Pwr
Motors
Blower
Conv
(each)
Motor
Outlet
MCC
FLA
FLA
FLA
16.3
2.3
6
0
16.3
2.3
6
0
21.4
2.3
7.6
0
21.4
2.3
7.6
0
24.9
2.3
7.6
0
24.9
2.3
7.6
0
Electric Heat Option
Model
kW
Stages
Amps
NONE
-
-
E05
4
1
11.1
E07
5.6
1
15.5
E10
8
1
22.2
E15
11.9
2
33
E20
15.9
2
44.1
NONE
-
-
E05
5.3
1
12.7
E07
7.5
1
18
E10
10.6
1
25.5
E15
15.9
2
38.2
E20
21.2
2
51
NONE
-
-
E05
4
1
11.1
E07
5.6
1
15.5
E10
8
1
22.2
E15
11.9
2
33
E20
15.9
2
44.1
NONE
-
-
E05
5.3
1
12.7
E07
7.5
1
18
E10
10.6
1
25.5
E15
15.9
2
38.2
E20
21.2
2
51
NONE
-
-
E05
4
1
11.1
E07
5.6
1
15.5
E10
8
1
22.2
E15
11.9
2
33
E20
15.9
2
44.1
E30
22.2
2
61.6
NONE
-
-
E05
5.3
1
12.7
E07
7.5
1
18
E10
10.6
1
25.5
E15
15.9
2
38.2
E20
21.2
2
51
E30
29.6
2
71.2
Max
2
Fuse
/
1
MCA
3
Breaker
(Amps)
Size
(Amps)
-
21.3
30
21.4
30
26.9
30
35.3
40
48.8
50
62.7
70
-
21.3
30
23.4
30
30.1
35
39.4
40
55.3
60
71.2
80
-
27
35
27
35
28.9
35
37.3
40
50.8
60
64.7
70
-
27
35
27
35
32.1
40
41.4
45
57.3
60
73.2
80
-
29.9
40
29.9
40
29.9
40
37.3
45
50.8
60
64.7
70
86.5
90
-
29.9
40
29.9
40
32.1
40
41.4
45
57.3
60
73.2
80
98.5
100