York International ZK Series Installation Manual page 18

R-410a, 3 - 5 ton, 60 hertz
Table of Contents

Advertisement

5121817-TIM-A-0515
ZKT03 Thru T05 Without Powered Convenience Outlet (Belt Drive High Static)
Compressors
Size
(each)
Volt
(Tons)
RLA LRA
208-3-60 10.4
73
230-3-60 10.4
73
T03
(3.0)
460-3-60 5.8
38
575-3-60 3.8
36.5
208-3-60 13.7
83.1
230-3-60 13.7
83.1
T04
(4.0)
460-3-60 6.2
41
575-3-60 4.8
33
18
OD Fan
Supply
Pwr
Motors
Blower
Conv
(each)
Motor
Outlet
MCC
FLA
FLA
FLA
16.3
2.3
5.2
0
16.3
2.3
5.2
0
9
1.3
2.6
0
5.9
1.3
2
0
21.4
2.3
5.2
0
21.4
2.3
5.2
0
9.7
1.3
2.6
0
7.5
1.3
2
0
Electric Heat Option
Model
kW
Stages
Amps
NONE
-
-
E05
4
1
11.1
E07
5.6
1
15.5
E10
8
1
22.2
E15
11.9
2
33
E20
15.9
2
44.1
NONE
-
-
E05
5.3
1
12.7
E07
7.5
1
18
E10
10.6
1
25.5
E15
15.9
2
38.2
E20
21.2
2
51
NONE
-
-
E07
6.8
1
8.2
E10
10.1
1
12.1
E15
13.6
2
16.4
E20
19.5
2
23.5
NONE
-
-
E10
10.6
1
10.2
E15
15.9
2
15.3
E20
21.2
2
20.4
NONE
-
-
E05
4
1
11.1
E07
5.6
1
15.5
E10
8
1
22.2
E15
11.9
2
33
E20
15.9
2
44.1
NONE
-
-
E05
5.3
1
12.7
E07
7.5
1
18
E10
10.6
1
25.5
E15
15.9
2
38.2
E20
21.2
2
51
NONE
-
-
E07
6.8
1
8.2
E10
10.1
1
12.1
E15
13.6
2
16.4
E20
19.5
2
23.5
NONE
-
-
E10
10.6
1
10.2
E15
15.9
2
15.3
E20
21.2
2
20.4
Max
2
Fuse
/
1
MCA
3
Breaker
(Amps)
Size
(Amps)
-
20.5
25
20.5
25
25.9
30
34.3
35
47.8
50
61.7
70
-
20.5
25
22.4
30
29.1
30
38.4
40
54.3
60
70.2
80
-
11.1
15
13.5
15
18.4
20
23.7
25
32.6
35
-
7.8
15
15.2
20
21.6
25
28
30
-
24.6
30
24.6
30
25.9
35
34.3
35
47.8
50
61.7
70
-
24.6
30
24.6
30
29.1
35
38.4
40
54.3
60
70.2
80
-
11.6
15
13.5
15
18.4
20
23.7
25
32.6
35
-
9
15
15.2
20
21.6
25
28
30
Johnson Controls Unitary Products

Advertisement

Table of Contents
loading

Table of Contents