Toshiba RemotEye 4 Procedure For Installing page 3

On g9000 series ups (pre-installed brackets)
Hide thumbs Also See for RemotEye 4:

Advertisement

2.0 LOCATE REMOTEYE MOUNTING PLATE & BRACKET
This step gives instructions for locating the RemotEye Mounting Plate in any of the G9000
Series UPS.
2.1 Ensure that power is being provided to the G9000 UPS.
2.2 Open the G9000's door, and remove the dead front cover (if any) covering the display PCBs
on the inside of the door.
2.3 Reference Figure 4 through Figure 9 to determine the specific location of the RemotEye 4
mounting location as well as the mounting holes for the ribbon cable bracket (shown within
the red ellipse). The mounting plate and bracket are pre-installed in this area. Note: as shown
in Figure 9, the 1000kVA mounting location is in the unit itself, not the reverse side of the
door.
Instructions for G9000 Series UPS RemotEye – 90000-004
Figure 4: 100/160kVA RemotEye 4 Location
Figure 5: 225kVA RemotEye 4 Location
Page 3 of 8