Download Print this page

Eaton Cutler-Hammer G Series Instruction Leaflet page 3

J-frame motor operator

Advertisement

Page 3
6
PUSH-TO TRIP Button
Status
Indication
Manual Operations
• Move the slide knob to the MANUAL position to expose the manual operating shaft located under
the slide knob. The control power supply is cut off automatically.
• Insert the operating key into shaft slot. Turn the key clockwise to verify the breaker can be closed
and opened.
• Leave breaker in the ON position. Press the manual PUSH-TO-TRIP button on the motor operator
to trip the breaker. Check that the display indicates the TRIP position.
• Turn the operating key clockwise (approximately 180
• Status window indicates Green / OFF, Red / ON and White / Tripped.
• Always remove the operating key and move the slide knob to the AUTO position before operating
electrically.
Effective Date 11/07
Opetating key
Turn the key
(Clockwise only)
°
) again. This should reset the breaker.
IL01222026E
Slide knob