8
Electrical Operation
• Make sure the slide knob is located in the AUTO position.
• Operating the OFF remote control switch will cause the breaker to go to its OFF position.
• Operating the ON remote control switch will cause the breaker to go to its ON position.
• Press the manual PUSH-TO-TRIP button on the motor operator to verify that the breaker moves to
the trip position. Operating the OFF remote control switch again will reset the breaker.
• Status window indicates Green / OFF, Red / ON and White / Tripped.
• Always remove the operating key and move the slide knob to the AUTO position before operating
electrically.
9
Effective Date 11/07
LOCK-OFF
Move slide knob to AUTO position. Pull out
the Lock-Off lever when breaker is in OFF
position, insert one to three padlock shackles
up to 6mm (.25 inch) in diameter.
CAUTION
The motor operator cannot be locked off
while it is in the ON position.
Lock-Off Lever