1.2.1 > Charger In summary / I Load / associated battery capacity
rated current (A) ↓
RMS IP 12V 8A à 16A UTIL
24A
RMS IP 12V 16A à 32A UTIL
48A
RMS IP 24V 4A à 10A UTIL
12A
RMS IP 24V 10A à 16A UTIL
24A
RMS IP 48V 2A à 4A UTIL
6A
RMS IP 48V 4A à 10A UTIL
12A
RMS IP 56V 2A à 4A UTIL
6A
Note: inferior capacity batteries can also be used.
1.3 Environmental specifications
Operating temperature:
-5 °C to 40°C at 100 % charge.
-5 °C to +50 °C at 75 % charge.
Storage temperature: -25 to +85°C.
Relative humidity: 20 to 95%.
1.4 Electrical input and output specifications
1.4.1 Network input
single-phase voltage: 98V to 264V
-
-
frequency: 47 to 63 Hz.
class I.
-
-
neutral systems: TT, TN, IT.
Primary current @ 98V
Primary current @ 195 V
Circuit breaker to be provided upstream: D curve
1.4.2 Output
Rated voltage
Floating voltage set at half-load and at 25 °C
Adjustment range (V)**
Limitation current
AUX output current (max)
* RMS IP 56V 2A à 4A UTIL model includes a converter which maintains a constant voltage at the load terminals.
** Only possible without batteries connected. All use of the adjustment range (in charger mode) with
batteries connected will damage the battery.
using current (A) →
2
4
Max charging current (A)
battery Max capacity (Ah)
Max charging current (A)
battery Max capacity (Ah)
Max charging current (A)
8
battery Max capacity (Ah)
80 Ah 60 Ah 40 Ah
Max charging current (A)
battery Max capacity (Ah)
Max charging current (A)
4
2
battery Max capacity (Ah)
40 Ah 20 Ah
Max charging current (A)
8
battery Max capacity (Ah)
80 Ah 60 Ah 40 Ah
Max charging current (A)
4
2
battery Max capacity (Ah)
40 Ah 20 Ah
300W
600W
4A
8A
2A
4A
Code : 180140005Ca - NDU :
Edition : 03/18
6
8
10
12
14
16
16
14
12
10
8
160 Ah 140 Ah 120 Ah 100 Ah 80 Ah
32
320 Ah 300 Ah 280 Ah 260 Ah 240 Ah 220 Ah 200 Ah 180 Ah 160 Ah
6
4
2
20 Ah
14
12
10
8
140 Ah 120 Ah 100 Ah 80 Ah
6
4
2
20 Ah
12V
24V
13.6V +/-0.5 % 27.2V +/-0.5 %
12 - 14V
23 - 29V
55
NOT140004Ca
18
20
22
24
26
28
30
28
26
24
22
20
48V
54.4V +/-0.5
54.4V +/-0.5%
%
46 - 58V
In
5A
30
32
18
16
56V*
46 - 58V