Troubleshooting - Greenheck Grease Trapper ESP Installation, Operation And Maintenance Manual

Kitchen exhaust pollution control system
Table of Contents

Advertisement

Troubleshooting

Problem: Cells shorting immediately (Green indicator light continually flashes)
Cells are dirty/clogged
Cells are not installed correctly
Cell wiring incorrect
Dry portion of wash cycle was bypassed
Problem: When running unit, green indicator on terminal enclosure illuminates, then after a few seconds turns off,
then repeats
Power supply is not providing correct voltage
back to control panel
Problem: Indicator lights (LEDs) on terminal enclosures not illuminating
Wiring not matching polarity of LEDs
Faulty LEDs or faulty power supply
Problem: Power supplies operating (green), but cells don't appear to be collecting contaminants
Insufficient connection between
cells or plugs
Problem: Cells not fully clean after completed wash cycle
Detergent empty
Incorrect detergent used
Wash sequences are too short for cooking
duty
Water temperature or pressure incorrect
Problem: Wash cycle won't start via button, digital input, nor the wash scheduler
Fans are running
System in fire mode
Wash cycle is starting, but water isn't turned
on to unit
Problem: Unit not washing
Something is preventing the wash from
occuring
®
Run through a wash, making sure detergent level is full. If cells are still dirty, safely
removing cells and manual cleaning/spraying may be necessary. If air compressor
is available on site, spray out cells thoroughly of any dust and debris.
Safely remove cells and make sure they are installed correctly, ensure the cell
pushers are installed tightly with no slack in the cable. Cable could short out on
collector ionizer rods to the ground if installed incorrectly, see page 7.
IONIZER should be connected to the RED spark plug cable (Ionizer is the spiked
smaller plates that face the inlet of the unit) COLLECTOR should be connected to
the BLUE spark plug cable. GROUND cable should be connected to the BLACK
spark plug cable. Cells have been labeled by the laser to indicate each spark
plug connection.
If the unit dry portion of the wash cycle was bypassed, the cells may still be wet.
Run the fan for 60 – 90 minutes to dry out the cells.
Possible faulty or incorrectly programmed power supply. Contact factory for
further troubleshooting assistance.
Switch the leads on the LEDs located on the cover of the terminal enclosure(s).
Test voltage to LEDs and to input power of power supply when unit is on.
Replace LEDs/power supply if faulty.
Ensure spark plug style cables are properly connected, and that the cell pusher is
properly installed.
Check to see if there is a low detergent alarm, refill detergent if empty
Make sure detergent used is the recommended Zep X701
Increase wash sequence times
Make sure water temperature is 140°F and 40 psi
Fans need to be turned off before wash can be started
Check for fire micro-switch wiring (normally-closed contact between C1 and
NC1).
Confirm wash is running by referencing keypad/touchscreen. Check hot water
shut off valves feeding the unit.
Review wash history pages on controller, see page 17-18 for more details.
Grease Trapper ESP™ Kitchen Exhaust Pollution Control System
35

Advertisement

Table of Contents
loading

Table of Contents